Installation

3.05

Comfort Plus Hydronic

Comfort Plus Hydronic

Installation

3.06

SAMPlE SYSTEM IDENTIFICATION lABEl

FIgUrE 8

JuNCTION BOx INSTAllATION
Step 1
Attach the factory supplied junction box to the left side of the Comfort Plus Hydronic system as shown

in Figure 16 (Page 3.12).

Step 2 Make connections to the primary loop pump and air handler pump inside this junction box. The red and

white wires connect to the primary loop pump and the black and white wires connect to the air handler

pump. (See Figure 10.) The maximum connected amperage on either of these circuits is 1.2 amps.

Step 3 Attach the junction box cover using the screws provided.

If utilizing the optional air handler, the orange wire can be used with the white wire to power a

secondary pump for hydronic zones.

CIrCUIT PHASINg CONNECTIONS

FIgUrE 9

NOTE: The controls

circuit MUST

include a

neutral wire.

To ensure proper operation and safety, all line voltage circuits must be segregated from low voltage

wiring in the Comfort Plus Hydronic.

To reduce electro magnetic fields associated with electrical circuits and to avoid induced voltage on

sensors and electronic devices, the circuit phases MUST be alternated as shown in Figure 9.

IMPORTANT

lINE VOlTAgE WIrINg DIAgrAM

FIgUrE 10

Comfort Plus Hydronic

Circuit Breakers

LINE 2

LINE 1

LINE 2

LINE 1

CHARGE CIRCUIT #3

CHARGE CIRCUIT #2

CHARGE CIRCUIT #1

CONTROLS CIRCUIT

CHARGE CIRCUIT #4

(MODEL 5130 and 5140 ONLY)
LINE 2

LINE 1

LINE 1

LINE 2

LINE 1

LINE 2

To Service (Breaker) Panel

NEUTRAL CONNECTION FOR CONTROL CIRCUIT

THIS MUST BE A 120/240V OR 120V/208V CIRCUIT

NEUTRAL

LUG

BLACK

COM

COM

HEATING ELEMENTS

Element 2
Element 1

Element 3

Element 4

NO

NO

75VA

240v 24v

TRANSFORMER

Element 7

Element 5

Element 6

Element 8

BLACK/YELLOW

LIMIT

WHITE/BLACK

CORE

L2 240

COM

COM

NO

NO

L2 120

RED

These wires are located on the lower left

side of the system near the inlet pipe.

75° C or higher for field connections of this device.

Use copper or aluminum conductors rated at

Wiring Diagram 240/208 Volt

5120 Line Voltage

WHITE/BLACK

RED
BLACK

Red & White To

Primary Loop Pump

(Max 1.2 AMPS)

Black & White To Air

Handler Pump (Max 1.2 AMPS)

WHITE

OR

COM

COM

NO

NO

1/4 Amp

5 Amp

225 °

N.C.

AUTO

RESET

N.C.

RESET

MANUAL

EXCHANGER

LIMITS

HIGH

BLACK

Cap.

4uf

CORE BLOWER

NEUTRAL LUG

CIRCUIT #2

CIRCUIT #3

CHARGE

CIRCUIT #1

CHARGE

CIRCUIT

CONTROLS

BLOWERS/

CHARGE

60A

60A

15A

60A

CONTROL CIRCUIT

Element

Element

Element

1,8

Relays

2,4,6

Relays

3,5,7

Relays

To

To

To

ELEMENT 1

ELEMENT 2

ELEMENT 3

ELEMENT 4

ELEMENT 5

ELEMENT 6

ELEMENT 7

ELEMENT 8

BOARD

EXPANSION

#1

GROUND

LUGS

L1

OR

WHITE

ORANGE

COM

COM

BLACK

BLACK/YELLOW

CORE

LIMIT

COM

1/4 Amp

L1

COM

NO

COM

COM

NO

NO

NO

RED

BLUE/WHITE

BLUE/BLACK

ORANGE

ORANGE

DAMPER

RESISTER

RESISTOR

SHRU

LOOP PUMP

PRIMARY

BLACK

BLUE

RED

COM.

WHITE

250 °

BLUE

BLACK/YELLOW

RED

WHITE/BLACK

BLOWER

L2 240

L2 120

NO

NO

Advertising
This manual is related to the following products: