Caution – Steffes 5140 Owner & Installers Manual User Manual

Page 24

Advertising
background image

C006

Output Control Configuration - Configures the output controls of the Comfort Plus Hydronic system.

To determine the value, check the options desired from the list below. Then, add the numbers from the

“Value” column and enter the sum into this location. If not used in conjunction with a heat pump or air

conditioner, the value in this location should be set to two (2).

Value Option Selected

2

All Comfort Plus Hydronic Systems (5100 Series)

8

Enables compressor control if there is a "COOL" call during a peak (control) time.

32

If a peak (control) period and a cooling call, the compressor will turn off and on in 20

minute intervals (off 20 minutes, on 20 minutes, off 20 minutes, etc.).

128

Interfaces Comfort Plus Hydronic with a heat pump that has a reversing

valve which is energized for heating.

C007

Charge Factor - This configuration should be set to a value of 30.

C008 through C009 configurations are only applicable if the Comfort Plus Hydronic system is

being used in conjunc

t

ion with a heat pump.

C008

Heat Pump Compressor Outdoor lock-Out Temperature for Off-Peak or Anticipated Peak Modes

- Indicates the outdoor temperature at which the heat pump’s compressor is locked out and not allowed to

operate during an off-peak or ant

i

cipated peak period.

C009

Heat Pump Compressor Outdoor lock-Out Temperature for On-Peak Mode - Indicates the outdoor

temperature at which the heat pump’s compressor is locked out and not allowed to operate during an on-

peak period.

C010

Minimum Discharge Air Temperature - Sets the minimum discharge air temperature the system targets

during a Stage 1 heat call if using an air handler.

C011 and C012 configurations must be set for the

hottest temperature zone in the installation. C011

is the highest temperature the system will target

and C012 is the lowest temperature the system

will target during a heat call. Outdoor reset is

done using these two temperatures. (See graph.)

C011

Maximum Outlet Water Temperature - The value set indicates

the maximum outlet water temperature to be targeted. The targeted

outlet water temperature is affected by the values in C001 and

C002. For example, if the value in C001 = 50; C002 = 10; C011

= 180; C012 = 140, then at an outdoor temperature of 30 degrees,

the targeted outlet water temperature would be 160 degrees.

C012

Minimum Outlet Water Temperature - The value set indicates

the minimum outlet water temperature to be targeted. The targeted

outlet water temperature is affected by the values in C001 and

C002. For example, if the value in C001 = 50; C002 = 10; C011

= 180; C012 = 140, then at an outdoor temperature of 30 degrees,

the targeted outlet water temperature would be 160 degrees.

C013-C021 Time Clock Module Configuration - These configuration settings are used to configure the peak

control times when utilizing the optional Steffes Time Clock Module. Refer to the installation and

configuration instructions included with the module for more information

.

208V SYSTEMS ONlY:

In standard configuration, Steffes heaters are dual rated for 240V and 208V power connections.

The heaters are factory configured for 240V. If the control circuit is operating on 208V power, the

value in location 28 (l028) must be changed to 5.

CAUTION

Risk of high temperature

water. Can cause property

damage. Improper water

temperature settings can

result in damage to the floor

covering. Make sure the

maximum and minimum wa-

ter temperatures are appro-

priate for the application.

Installation

3.15

Comfort Plus Hydronic

Comfort Plus Hydronic

Installation

3.16

Example of Outdoor Reset

120

140

160

180

200

10

30

50

Outdoor Temperature

Water Temperature