Warning, Help menu, Error codes – Steffes 5140 Owner & Installers Manual User Manual

Page 35

Advertising
background image

Comfort Plus Hydronic

Appendix

A.10

HelP Menu

The Comfort Plus Hydronic system contains a "HELP" menu which may be accessed through the control panel. To

access the "HELP" menu, press and release the M button until the faceplate displays “HELP”. Scroll through this

menu by pressing either the up or the down arrow button.

Display

reading

Description

Fxxx

Firmware Version Number - Indicates the version of software installed.

O xx

Outdoor Temperature - Indicates current outdoor temperature as recognized by the system.

tL:xx

Target Level - Indicates the percentage of brick core charge level the system is targeting. During

peak periods the value displays as "tL_".

CL:xx

Charge Level - Indicates the percentage of heat storage currently in the brick core.

HE x

Heating Elements Active - Indicates the total number of heating elements currently energized.

PC x

Power Line Carrier Channel - Indicates the channel on which the system is set to receive PLC

communication signal.

P x

Power Line Carrier Net Hit Rate Percentage - Indicates the percentage of "GOOD" communication

packets received by the system from the PLC transmitting device.

PS x

Indicates which Specialty Timer the system is currently using. The value displayed will be zero if the

Specialty Timer is not being utilized.

CC_x

Charge Mode Operation - Indicates the charge control method being utilized during off-peak periods.

CA_x

A-Peak Mode Operation - Indicates the charge control method being utilized during anticipated peak

periods.

C1_x

Specialty Timer #1 Charge Mode - Specialty Applications Only

C2_x

Specialty Timer #2 Charge Mode - Specialty Applications Only

HUxx

Heat Usage - Indicates the percentage of input being dissipated by the system.

A_xx

Target Discharge Air Temperature - Indicates the discharge air temperature that the system is

targeting.

cxxx

Compressor Output Relay Delay Timer - Indicates time remaining before heat pump compressor is

energized. "c ON" indicates the heat pump is energized.

error coDeS

The Comfort Plus Hydronic system has an on-board diagnostic system to

monitor various operating conditions. If operating conditions move outside the

normal operating range, an error code is displayed on the faceplate. If there

are multiple errors simultaneously, only the highest priority error code appears.

Once corrected, the next highest priority code will be displayed. Error codes

will be displayed on the faceplate as “Er—” (i.e., Er05).

Error Code

Description

01

The lower core (Core A) thermocouple temperature is

out of normal operating range. This can be caused by

an open, shorted, or otherwise defective thermocouple

or a circuit board which is out of calibration.

02

The upper core (Core B) thermocouple temperature is

out of normal operating range. This can be caused by

an open, shorted, or otherwise defective thermocouple

or a circuit board which is out of calibration.

HAZARDOUS VOLT-

AGE: Risk of electric

shock. Can cause injury

or death. System may

be connected to more

than one branch circuit.

Disconnect power to all

circuits before servic-

ing. Equipment must be

serviced by a qualified

technician.

WARNING