Important, Configuration menu – Steffes 5140 Owner & Installers Manual User Manual

Page 23

Advertising
background image

confiGuration Menu

The Steffes Comfort Plus Hydronic heating system has a Configuration Menu,

which allows the system to be customized to the power company and consumer’s

needs. This menu can be accessed on start-up and allows configuration settings

to be easily adjusted.
To access the Configuration Menu:
Step 1 Energize the system. Access to the Configuration Menu is allowed

for the first two (2) minutes of operation. If the system has been

energized for more than two (2) minutes, the 15 amp circuit

breaker must be powered off and back on to gain access to this menu.

Step 2 Press and release the M button until the faceplate displays “CONF”.

Step 3 Press the up arrow once and the faceplate will display “C000”.

The faceplate will flash between “C000”

and the corresponding configuration value.

Step 4 If necessary, edit the configuration value by pressing and holding the M button while using the up or the

down arrow button to change the value.

Step 5 Once the value is correct, release the buttons and press the up arrow button to go to the next

configuration (C001,C002, etc.)

Step 6 Repeat steps 4 through 5 until all configuration settings have been adjusted to the desired values.

Step 7 Once configured, use the down arrow to leave the Configuration Menu.

In most applications only a few, if any, configuration changes will be necessary. Following is a description of the

configuration settings and their function:
C000

Off-Peak Method of Charge Control - Sets the method of brick core charging to be used during off-

peak (charge) periods. System is configured for automatic charge control which is a value of five (5).

C001

Start Brick Core Charge Set Point - If utilizing automatic charge control as set in C000, this value

indicates the outdoor temperature at which the system will start charging.

C002

Full Brick Core Charge Set Point - If utilizing automatic charge control as set in C000, this value

indicates the outdoor temperature at which the system will target a full core charge.

C003

Power line Carrier (PlC) Channel Selection - If using PLC communication, this setting must match

the channel setting in the Steffes PLC transmitting device. A value of zero indicates power line carrier

communication is disabled.

C004

Optional Controls Configuration

Value

Configuration Description

8 No Outdoor Sensor/No Time Clock Module

9 Outdoor Sensor/No Time Clock Module

12 No Outdoor Sensor/Time Clock Module (unlocks C013-C021)

13 Outdoor Sensor/Time Clock Module (unlocks C013-C021)

C005

Control Switch Configuration – If utilizing power line carrier control, the Steffes Time Clock Module,

line voltage peak control, or if the utility control switch opens for charging this value should be zero (0).

For all other applications, this value should be one (1).

Configuration Menu continued on next page...

If access to the Configuration

Menu times out, the 15 amp

circuit breaker must be

powered off and back on to

re-enter the menu.

IMPORTANT

Installation

3.13

Comfort Plus Hydronic

Comfort Plus Hydronic

Installation

3.14

Advertising
This manual is related to the following products: