The Comfort Plus Hydronic heating system MUST be plumbed with a primary loop and secondary (zone)

loops. The primary loop needs to consist of a minimum of 10' of 1" pipe and requires its own pump (circulator).

The secondary (zone) loops require additional pump(s) to operate effectively. Refer to Typical Primary Loop

(Figure 16) and the Typical System Plumbing Diagrams (Figures 17 and 18) for installation information.

The primary loop serves to regulate heat transfer from the system’s heat exchanger. The primary loop pump must

be powered by the Comfort Plus Hydronic control system as shown in Figure 17-18.

Step 1 Remove the exchanger access

panel and locate the pressure

relief valve assembly.

Step 2 Connect the pressure relief

valve to the outlet water port

on the left side of the Comfort

Plus Hydronic. It is extremely

important that the following conditions for installation

of this part are met:

• Ensure all connections, including the valve inlet

are clean and free from any foreign material.

• Use pipe compound sparingly, or tape on external

threads only.

• Mount the pressure relief valve in a vertical, up-

right, position directly to the outlet water port of

the system. Under no circumstances should there

be a flow restriction or valve of any type between

the safety relief valve and the pressure vessel.

Step 3 Use schedule 40 pipe to install a discharge line for the pressure relief valve. This discharge line MUST:

be connected from the valve outlet with no intervening valve and directed downward to a safe point

of discharge.

allow complete drainage of both the valve and the discharge line.

be independently supported and securely anchored to avoid applied stress on the valve.

be as short and straight as possible.

terminate freely to atmosphere where any discharge is clearly visible and is at no risk of freezing.

terminate with a plain end that is not threaded.

be constructed of a material suitable for exposure to temperatures of 375

o

F or greater.

PreSSure relief valve inStallation

Risk of discharged hot water and/or

steam. Can cause personal injury or

property damage. During operation,

the pressure relief valve may discharge

large amounts of steam and/or hot

water. To reduce the potential for bodily

injury or property damage, install a dis-

charge line.

CAUTION

Installation

3.11

Comfort Plus Hydronic

Comfort Plus Hydronic

Installation

3.12

WARNING

Risk of explosion. Can cause injury or death. The factory supplied

pressure relief valve MUST be connected to the system with the

supplied fittings.

DO NOT modify this assembly.

DO NOT cap, plug, or otherwise obstruct the outlet of the

pressure relief valve.

DO mount the pressure relief valve in a vertical, upright position.

This pressure relief valve is sized to service the needs of the

Comfort Plus Hydronic heating system. If multiple heating

systems are being used, pressure relief valving for the other system MUST be provided

separately.

Available Pressure

relief Valves

Minimum

BTU rating

Maximum

Operating Pressure

Order

Item #

30 PSI

400,000

20 PSI

1100104

75 PSI

500,000

60 PSI

1100105

Note: 5100 Series Systems are shipped with 30 pSI pressure relief valves.

If a different valve is required order the item number listed above.