Configuring the C-Series Controller

975-0004-01-02 Rev D

21

Automatic/Manual Battery Equalization (EQ) and Low Voltage
Reconnect (LVR) Jumper

Depending on the mode of operation chosen, this jumper
enables:

automatic or manual battery equalization
(Charge Control mode), or

automatic or manual reconnect in the event of low
voltage event (Load Control mode).

When A

UTO

is enabled in the Charge Control mode, the unit

will perform an equalization charge every 30 days. This can
be done manually by using Reset Switch on the side of the
controller chassis.

When A

UTO

is enabled in Load Control mode, the unit will

reconnect automatically when voltage at the B

ATTERY

P

OSITIVE

terminal exceeds the LVR setting. This can also be

done manually by using Reset Switch on the side of the
controller chassis.

The factory default setting is M

ANUAL

E

QUALIZATION

(Charge Control mode).

Place the jumper over the pins for the desired selection.

See

“Error Mode Indication (Orange)” on page 59

for

instructions on how to use the Reset Switch in relation to this
function.

Figure 2-8 EQ/LVR Jumper and Reset Switch

EQ/LVR Jumper

MANUAL

AUTO