Minimumrecommendedwiregauge, Surge protection, Minimum recommended wire gauge surge protection – Windy Nation Xantrex C Series Multifunction DC Controller User Manual

Page 60: Figure 2-22, Awg wire gauge reference chart, Minimum recommended wire gauge

Advertising
background image

Installation

40

975-0004-01-02 Rev D

Minimum Recommended Wire Gauge

The minimum recommended wire gauge is:

C35 and C40 Models:
#8 AWG with a 75 °C (167 °F) insulation rating

C60 Models:
#6 AWG, with a 90 °C (194 °F) insulation rating

The terminals on the

C-Series

will accept up to #2 AWG

(33.6 mm

2

) copper or aluminum wire. However, UL

specifications only allow the use of up to #6 AWG
(13.3 mm

2

) maximum.

No crimp-on terminals or lugs are required.

Surge Protection

Since PV arrays are often mounted on an elevated structure
and thus are more susceptible to lightning strikes, protection
from lightning-induced power surges and other transient
power disturbances between the PV array and the

C-Series

Figure 2-22 AWG Wire Gauge Reference Chart

Important:

Figure 2-22

is for reference only. Sizes shown are

for the conductor. Do not include any insulation when
determining your wire size. Due to printing anomalies, these
dimensions may not be to scale.

12

.072

10

.115

8

.146

6

.184

4

.235

14

.073

Size

Diameter

3

.281

2

.295

3/0

.475

4/0

.530

2/0

.420

1

.335

1/0

.380

Size

Diameter

Advertising