Adjusting the C-Series Voltage Settings

975-0004-01-02 Rev D

29

For example for a 48-volt system:

To set BULK voltage to 56.4 volts:

1.

Point the BULK potentiometer to the mid-range position.

2.

Adjust the potentiometer until the DVM displays
1.1 volts (1.1 x 4 [48 volt] = 4.4 + 52.0 = 56.4).

Figure 2-15 Test Points for Adjusting Voltage Using a DVM

Battery Common Negative
Terminals

TEST POINTS for DVM
(center legs of