Diversion control mode wiring – Windy Nation Xantrex C Series Multifunction DC Controller User Manual

Page 66

Advertising
background image

Installation

46

975-0004-01-02 Rev D

Diversion Control Mode Wiring

The procedure below is illustrated in

Figure 2-24

.

When using the

C-Series

unit as a Diversion or DC Load

Controller, the DC load needs to be connected to the
controller terminals marked as

PV

+/

LOAD

+ and

COMMON

NEGATIVE

.

To connect the

C-Series

as a diversion load controller:

1.

Connect your DC current source (PV, wind, hydro, etc.)
directly to the RE disconnect.

2.

Connect another cable from the other side of the RE
disconnect to the battery positive terminal.

3.

Run a negative wire from the DC current source (PV,
wind, hydro, etc.) to the battery negative terminal.

4.

Connect a cable from controller terminal marked BAT
POS to the battery disconnect.

5.

Connect a cable from the battery disconnect to the
positive terminal of the battery.

6.

Connect a cable from the negative battery terminal to one
of the terminals marked C

OMMON

N

EGATIVES

on the

controller’s circuit board.

7.

Connect a cable from the controller’s other terminal
marked C

OMMON

N

EGATIVES

to the negative terminal of

your DC diversion load.

8.

Connect a cable from the controller’s terminal marked
PV+/LOAD+ to the positive terminal of your DC
diversion load.

9.

Tighten per torque requirements outlined on

page 39

.

Allow a little slack on the cables within the controller and
secure the wiring with strain reliefs.

Important:

Do not use light bulbs for diversion loads. Use

only resistive loads such as air- or water-cooled heating elements

Advertising