Setting Voltage Parameters for Load Control Mode

To change the Low Voltage Disconnect (LVD) and Low
Voltage Reconnect (LVR) settings, use the same BULK and
FLOAT potentiometers. However, when the

C-Series

controller

is used for DC Load Control, the potentiometer’s

scale calibration is altered from what is printed on the circuit
board.

A decal is provided with the

C-Series

with the proper scale

calibrations for the Load Control mode. The BULK
potentiometer becomes the Low Voltage Reconnect (LVR),
and the FLOAT potentiometer becomes the Low Voltage
Disconnect (LVD).

Place the sticker provided over the potentiometers. The knobs
may have to be removed for sticker placement, then
reinstalled. The sticker is packed inside the

C-Series

controller

(bottom of unit). If the decal is lost or unavailable,

you can recalculate the appropriate voltage settings as
follows:

The scale for the Low Voltage Reconnect setting is calibrated
as follows:

12-volt system: 12.0 to 14.0 volts
in increments of 0.2 volts,

24-volt system: 24.0 to 28.0 volts
in increments of 0.4 volts,

48-volt system: 48.0 to 56.0 volts
in increments of 0.8 volts.

Figure 2-11 Potentiometers with Decal for LVR and LVD Settings

LVR Setting

LVD Setting

BULK Setting
Potentiometer

FLOAT Setting
Potentiometer