Over-currentprotection, Over-current protection, Table 2-3 – Windy Nation Xantrex C Series Multifunction DC Controller User Manual

Page 61: Minimum wire size

Advertising
background image

Wiring

975-0004-01-02 Rev D

41

controller

are strongly recommended. Put a surge protection

device on the input line of the

C-Series controller

between

the PV array and the controller.

If the battery, is over 15 feet away from the controller, or if it
is routed next to other wiring or sources of power, additional
surge protection devices are recommended. Put the surge
protection device for this scenario on the battery input line
between the battery and the controller.

Over-current Protection

The NEC requires conductors and over-current devices be
operated at no more than 80% of their rating. Refer to

Table

2-3

for a listing of the minimum wire size and over-current

device ratings to be used for each model.

As a minimum, a 60-amp DC-rated current-limiting fuse or
circuit breaker should be installed near the battery for
protection from short circuits. To meet NEC requirements,
use a 60 amp circuit breaker listed for 100% duty for the C60.
To meet UL requirements, use #6 AWG copper wires rated
for 90 °C (194 °F) for the C60. Over-current protection for
the battery circuit is to be provided by others. Refer to

Table 2-3

for the correct ratings of the fuse and circuit

breaker.

Table 2-3 Minimum Wire Size

Controller

Minimum Wire Size

Over-Current Device Rating

C35

#8 AWG

45 amps

C40

#8 AWG

50 amps

C60

a

a.To meet UL requirements, use #6 AWG, (90 °C/194 °F) wire and a 60 amp Listed 100%
duty over-current device for the C60 controller.

#6 AWG (90 °C/194 °F wire)

60 amps (listed 100% duty)

C60

#4 AWG

b

(75 °C/167 °F wire)

b.Not approved by UL for direct connection into the controller. Use a splicer block and #6
AWG (90 °C/194 °F) wire to connect to the controller terminals.

60 amps (listed 100% duty)