KEYENCE DL-EP1 User Manual

Page 32

Advertising
background image

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -

3-2 DL-EP1 EtherNet/IP Communication Function

3-4

3

Commu

nic
ati

ng

wi

th t
he SK-1000

S

eries

Cyclic communication

This function sends and receives data between the scanner and DL-EP1 at the set

RPI (Requested Packet Interval). The function can exchange data such as the

sensor amplifier's output signals and judgment values and error status without ladder

programs.

Configurations such as RPI and data size for cyclic communication are set
on the scanner side.
In a network which has many connected devices, including EtherNet/IP
devices, a delay or packet loss could occur if a large load is constantly or
temporarily applied on the network. Verify the settings carefully before
operation.

Message communication

Message communication can be used for applications which do not require a

punctuality like cyclic communication.

In message communication, various parameters, including data which can be

exchanged with cyclic communication, can be read and written. Functions specific

to sensors such as the sensor amplifier preset function can also be executed.

PLC

EtherNet/IP scanner

RPI=3 (ms)*

RPI=0.5 (ms)*

RPI=5 (ms)*

RPI=10 (ms)*

Various EtherNet/IP adaptors

Ethernet

* RPI (Requested Packet Interval) can be set
individually for each connection.

Point

Advertising