KEYENCE DL-EP1 User Manual

Page 61

Advertising
background image

3-4 Message Communication

3-33

3

Commu

nic
ati

ng

wi

th t
he SK-1000

S

eries

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -

Lock setting

Responses

The responses made when each service is used are as follows:

(1) Parameter read:

: Service code 0EH

(2) Parameter write:

: Service code 10H

(3) Operation command:

: Service code 4BH

(4) Batch lock setting:

: Service code 4CH

(5) Read of number of decimal places: : Service code 4DH

Setting

Description

0

Does not execute lock.

1

Executes key lock (inhibition of operations other than basic screen display

switching and [RESET] button).

General

Status

Command Type

Description

(1) (2) (3) (4) (5)

00H

Normal end

05H

The instance ID is out of range.

08H

-

-

-

The designated instance ID does not support this service or

cannot be executed.

09H

-

-

-

-

The written data is out of range.

0CH

-

-

-

Parameter write was executed for the function controlled

by cyclic communication.

An attempt to execute the operation command has failed.

Check if the sensor amplifier can execute the operation

command.

0EH

-

-

-

-

An attempt was made to write data to the attribute ID that

cannot be written or to the attribute ID that is in the unwritable

status.

10H

-

-

-

-

An attempt was made to read data from the attribute ID that

cannot be read or from the attribute ID that is in the

unreadable status.

13H

-

-

The service data size is less than the defined size.

The defined data size is stored in the additional status.

14H

-

The attribute ID is out of range.

16H

-

The sensor amplifier corresponding to the designated

instance ID is not connected.

1FH

This service is supported by the designated instance ID

but cannot be used by the designated attribute ID.

(Additional status: C350H)

In the current mode, the designated setting cannot be

written into the parameter.

(Additional status: C351H)

The DL-EP1 is now initializing communication. (Additional

status: C352H)

FEH

System error. Contact your nearest KEYENCE office.

Advertising