3-4 Message Communication

3-41

3

Commu

nic
ati

ng

wi

th t
he SK-1000

S

eries

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -

Group3

0369H

(873)

System

parameter

settings

*7

Set up system parameter.

To reflect the setting, you need to send

"System parameter set request" (0306H (774))

operation command after writing the setting.

Use 0338H (824) to check the system

parameter with which the sensor amplifier is

operating.

bit 0:

0: NPN

1: PNP

bits 1, 2 and 3 (For main unit only. Fixed to 000

for expansion unit)

000: Analog output OFF

001: 0 to 5V

010: -5 to 5V

011: 1 to 5V

100: 4 to 20mA

R/W

DINT

036AH

(874) to

037FH

(895)

(Reserved for system)

Group4

0380H

(896)

Group4 Entry

count

Indicates the No. of Group 4 entries.

Parameter range: 26

R

DINT

0381H

(897)

(Reserved for system)

0382H

(898)

Range setting

Set up measurement range.

Parameter range: 0 to 2 (initial value: 0)

0: NEAR

1: FAR

2: Ib

R/W

DINT

0383H

(899) to

0384H

(900)

(Reserved for system)

0385H

(901)

Averaging

Set up averaging/diff. count filter/high-pass

filter.

Parameter range: 0 to 8 (initial value: 5)

0: 1 time

1: 2 times

2: 4 times

3: 8 times

4: 16 times

5: 64 times

6: 256 times

7: 1024 times

8: 4096 times

9: 16384 times

R/W

DINT

0386H

(902)

Output mode

Set up output mode.

Parameter range: 0 to 1 (initial value: 0)

0: N.O.

1: N.C.

R/W

DINT

0387H

(903)

(Reserved for system)

0388H

(904)

Hold function

setting

Set up hold function.

Parameter range: 0 to 5 (initial value: 0)

0:Sample hold

1:Peak hold

2:Bottom hold

3:Absolute value hold

4:Auto peak hold

5:Auto bottom hold

6:Auto absolute value hold

R/W

DINT

Class

Attribute

ID

Name

Description

Attribute

Data

Type

Advertising