Ethernet/ip settings parameters, Ethernet/ip, Settings parameters – Comtrol IOLM 4-EIP User Manual

Page 35

Advertising
background image

IO-Link Master 4-EIP User Guide: 2000582 Rev. A

Chapter 5. IO-Link Port Configuration - 35

EtherNet/IP Settings Parameters

5.2.2. EtherNet/IP Settings Parameters

The EtherNET/IP Settings configuration page supports the following options.

EtherNet/IP Settings Page

ISDU Data Settings

ISDU Response Timeout

Default: 20 seconds

The time that the IO-Link Master’s EtherNet/IP interface waits for a
response to an ISDU request.

The timeout needs to set long enough to allow all commands within the
ISDU request to be processed.

Valid range: 1-10,000 seconds

Process Data Settings

PDI Data Block Size (To PLC)

Default: 36-bytes

The configurable PDI data block length. Supported optional lengths are:

4-bytes (header only)

8-bytes (4 bytes data)

16-bytes (12 bytes data)

24-bytes (20 bytes data)

36-bytes (32 bytes data)

PDI Data Block Format (To
PLC)

Default: Word-16

Data format of PDI data block to be transferred to the PLC(s) in Class 1
and/or Write-to-Tag/File PDI Transfer Modes. Supported formats are:

Byte-8 (8-bit or SINT)

Word-16 (16-bit or INT)

Dword-32 (32-bit or DINT)

Note: The Data Block Format is independent of the PDI Data Byte-Swap

Method.

This setting is not used for the SLC, PLC-5 and MicroLogix PLCs
which are always Word-16.

PDI Data Byte-Swap Method

Default: Work (16-bit) byte swap

If enabled, the IO-Link Master swaps the data bytes in word (2 byte)
format or dword (4 byte) format.

Supported values are:

No byte-swap – data passed through as received

Word (16-bit) byte-swap – data is byte-swapped in word format

Dword (32-bit) byte-swap – data is byte-swapped in dword format

Note: The byte swapping must be set correctly in order to convert from IO-

Link (big-endian byte order), to EtherNet/IP (little-endian byte
order).