IO-Link Master 4-EIP User Guide: 2000582 Rev. A

Chapter 5. IO-Link Port Configuration - 39

EtherNet/IP Settings Parameters

Maximum PLC Update Rate

Default: 40ms

The maximum rate at which the IO-Link Master updates the PDI tag or
file.

This parameter is used to ensure that the PLC receives all state changes.

Setting the update rate to 10 ms effectively disables this feature. The
valid range is 10 to 65535 ms.

Heartbeat Update Enable

Default: False

If selected, the IO-Link Master updates the PDI data block at the
Heartbeat Update Rate.

False = Heartbeat update disabled

True = Heartbeat update enabled

Heartbeat Update Rate

Default: 1000ms

If Heartbeat Update Enable is selected, the rate at which the IO-Link
Master updates the PDI data block in the Write-to-Tag/File mode.

The valid range is 50 to 65535 ms.

Read PDO from Tag/File Settings

PDO Tag/File Name

Default: blank

The tag or file name that the IO-Link Master reads the PDO data block
from.

ControlLogix family:

-

Tags must be same type as PDO Data Format (SINT, INT or
DINT).

-

Tags must be an array.

-

Tags must be at least as long as the PDO Data Block Length.

SLC/PLC-5/MicroLogix:

-

Files must be of INTEGER (16-bit) type.

-

Files must be named with standard file name conventions (i.e:
N10:0, N21:30, etc)

The file must be at least as long as the PDO Data Block Length.

PLC Poll Rate

Default: 1000ms

The frequency which the IO-Link Master reads the PDO data block in the
Read-from-Tag/File mode.

Valid range: 50-65535 ms

EtherNet/IP Settings Page (Continued)