Chapter 5. IO-Link Port Configuration - 43

Modbus/TCP Settings Parameters

Event Active Hold Time

Default: 1000 ms

If Clear Event Code After Hold Time is enabled, the time period an
event code is reported in the PDI block before it is cleared.

Valid range: 1-65535

Valid Units are:

ms (milliseconds)

sec (seconds)

min (minutes)

hours

days

Clear Event Hold Time

Default: 500 ms

Once an event code has been cleared, the time an event code stays
cleared in the PDI block before another event code can be reported.

Valid range: 1-65535

Valid Units:

ms (milliseconds)

sec (seconds)

min (minutes)

hours

days

Transfer Mode Settings

Slave Mode Device ID

Default: 1

The Modbus Device ID used to access this IO-Link port.

Range: 1-247

PDI Receive Mode(s)

Default: Slave

Determines which PDI Receive (To PLC) Modes are enabled.

The selectable modes is Slave.

Note: Not selecting slave mode disables Modbus/TCP access to the

PDI data block.

PDO Transmit Mode

Default: Slave

Selectable Modes are:

Disabled

Slave

Modbus/TCP Settings Page (Continued)