Comtrol IOLM 4-EIP User Manual

Page 48

Advertising
background image

48 -

Chapter 7. Using the Diagnostics Pages

IO-Link Master 4-EIP User Guide: 2000582 Rev. A

IO-Link Port Diagnostics

The following table provides information about the IO-Link Diagnostics page.

IO-Link Diagnostics

Port Mode

Displays the active device mode:

Reset = The port is configured to disable all functionality.

IO-Link = The port is configured to IO-Link mode.

Digital In = The port is configured to operate as a digital input.

Digital Out = The port is configured to operate as a digital output.

Port Status

Displays the port status:

Inactive = The port is in active state. Typically, this indicates that the
device is either not attached or not detected.

Initializing = The port is in the process of initializing.

Operational = The port is operational and, if in IO-Link mode,
communications to the IO-Link device has been established.

PDI Valid = The PDI data is now valid.

Fault = The port has detected a fault and is unable to re-establish
communications.

Device Vendor Name

Displays the Device Vendor Name as stored in ISDU Index 16.

Device Product Name

The Device Product Name as stored in ISDU Index 18.

Device Serial Number

The Device Serial Number as stored in ISDU Index 21.

Device Hardware

The Device Hardware Version as stored in ISDU Index 22.

Device Firmware

The Device Firmware Version as stored in ISDU Index 23.

Device IO-Link Version

The supported Device IO-Link Version as stored in ISDU Index 0.

Auxiliary Bit Status

The current status of the auxiliary bit as received on Pin 2 of the IO-Link port.

Last Rx PDI Data (MS
Byte First)

The last Rx PDI data as received from the IO-Link device.

Device PDO Data Length

The supported Device PDO Data Length, in bytes, as stored in ISDU Index 0.

Lost PDO Controller(s)
Errors

The number of times that the PDO controller(s) were present and then lost
connection.

PDO Data Valid

Status of PDO data being received from controller(s).

Device PDI Data Length

The supported Device PDI Data Length, in bytes, as stored in ISDU Index 0.

PDI Data Valid

Current status of PDI data as received from the IO-Link device.

Last Tx PDO Data

The last Tx PDO data.

Time Since Initialization

The time since the last port initialization.

Lost Communication
Count

The number of times that communication has been lost to the IO-Link device.

Initialization Attempts

The number of times the IO-Link port was initialized.

Initialization Errors

The number of port initialization errors that occurred.

Process Data Errors

The number of process data errors the port received.

Process Data Retries

The number of process data retries the port performed.

Internal Communication
Errors

The number of IO-Link Master internal communication errors that occurred on
this port.

Device Communication
Errors

The number of device specific communication errors that occurred.

Advertising