Chapter 6. connecting devices, Devices – Comtrol IOLM 4-EIP User Manual

Page 45

Advertising
background image

IO-Link Master 4-EIP User Guide: 2000582 Rev. A

Chapter 6. Connecting Devices - 45

Chapter 6. Connecting Devices

The IO-Link Master provides four IO-Link ports with M12 connectors (5-pin female/A
coded).

Note: Make sure that you tighten the cables properly to maintain IP67 capabilities.

This table provides signal information for the IO-Link connectors.

This table provides information that you may need regarding the IO-Link connectors.

Note: IO-Link ports must have an approved cable or protective cover attached to the port guarantee IP67

compliance.

Pin

Signal

Description

1

L+

Power supply (+)

2

DI

Digital input

3

L-

Power supply (-)

4

C/Q

Communication signal, which supports
SDCI (IO-Link) or SIO (standard input/
output)

5

N/A

Not connected

Current and Power

Value

Maximum IO-Link Supply

200mA

Maximum C/Q Current:

High
Low

200mA

200mA

Peak C/Q Current:

High
Low

500mA

500mA

C/Q & DI Input:

Maximum
Minimum

Power Input +0.5VDC

-0.5VDC

SDCI (IO-Link) Transmission Rates:

COM1
COM2
COM3

4.8Kbps

38.4Kbps

230.4Kbps

Advertising