Chapter 5. IO-Link Port Configuration

IO-Link Master 4-EIP User Guide: 2000582 Rev. A

Modbus/TCP Settings Parameters

PDO Data Block Size

Default: 32-bytes

The configurable PDO data block length. Optional lengths are:

Event code not included:

4-bytes = 2 data words

8-bytes = 4 data words

16-bytes = 8 data words

24-bytes = 12 data words

32-bytes = 16 data words

34-bytes = 16 data words, 1 pad word

Event code included:

4-bytes = event code word, 1 data word

8-bytes = event code word, 3 data words

16-bytes = event code word, 7 data words

24-bytes = event code word, 11 data words

32-bytes = event code word, 15 data words

34-bytes = event code word, 16 data words

PDO Byte-Swap Method

Default: No byte-swap

If enabled, the IO-Link Master swaps the data bytes in word (2 byte)
format or dword (4 byte) format. Options include:

No byte-swap – data passed through as received

Word (16-bit) byte-swap – data is byte-swapped in word format

Dword (32-bit) byte-swap – data is byte-swapped in dword
format

Note: Because both IO-Link and Modbus/TCP use big-endian byte

ordering, byte swapping typically is not required for word and
dword data.

Byte swapping is most commonly required when sending byte
(8-bit) data to the IO-Link device and it is desired to send the
least significant byte of the holding register first. For these
cases, word (16 bit) byte-swap is typically used.

Append PDO to PDI Data

Default: False

If selected, the IO-Link Master appends any PDO data to the end of
the PDI data.

False = Do not append PDO data

True = Append PDO data

Clear Event Code in PDO Block

Default: False

If enabled, the IO-Link Master expects the first word of the PDO
block to be used for event code handling.

Values are:

True = expect event code

False = no event code, expect only PDO data

Clear Event Code After Hold Time

Default: True

If enabled, the IO-Link Master clears any event code reported in the
PDI data block after the Event Active Hold Time.

Values are:

True = clear event code after hold time

False = do not clear event code after hold time

Modbus/TCP Settings Page (Continued)