Comtrol IOLM 4-EIP User Manual

Page 38

Advertising
background image

38 -

Chapter 5. IO-Link Port Configuration

IO-Link Master 4-EIP User Guide: 2000582 Rev. A

EtherNet/IP Settings Parameters

Transfer Mode Settings

PDI Receive Mode(s)

Default: Polling, Class1

Determines which PDI Receive (To PLC) Modes are enabled. Supported
modes are:

Polling

Class1

Write-to-TagOrFile

PDO Transmit Mode

Default: Class 1

Supported modes are:

Off

PLC-Writes

Class1

Read-from-TagOrFile

Read/Write Tag/File Settings

PLC IP Address

Default: 0.0.0.0

The PLC IP Address is required if either Write-to-TagOrFile or Read-from-
TagOrFile
mode are enabled.

Format: xxx.xxx.xxx.xxx

PLC Controller Slot Number

Default: 0

The PLC Controller Slot Number is required if either Write-to-TagOrFile
or Read-from-TagOrFile mode are enabled.

Valid range: 0-64

PLC Type

Default: ControlLogix

Indicates the type of PLC that the tag(s) or file(s) are written to and/or
read from. Supported PLC Types are:

ControlLogix

SLC

PLC-5

MicroLogix

Write PDI to Tag/File Settings

PDI Tag/File Name

Default: blank

The tag or file name to place the PDI data block.

ControlLogix family:

-

Tags must be same type as PDI Data Format (SINT, INT or DINT).

-

Tags must be an array.

-

Tags must be at least as long as the PDI Data Block Length.

SLC/PLC-5/MicroLogix:

-

Files must be of INTEGER (16-bit) type.

-

Files must be named with standard file name conventions (i.e:
N10:0, N21:30, etc)

-

The file must be at least as long as the PDI Data Block Length.

Append PDO to PDI Data

Default: False

If selected, the IO-Link Master appends any PDO data to the end of the
PDI data.

False = Do not append PDO data

True = Append PDO data

EtherNet/IP Settings Page (Continued)