Warning, Fault relay – Comtrol ES8510-XTE User Manual

Page 109

Advertising
background image

RocketLinx ES8510-XTE User Guide: 2000574 Rev. C

Warning - 109

Configuration Using the Web Interface

Warning

The ES8510-XTE provides several types of warning features for you to remotely monitor the status of the
attached devices or changes in your network. The features include Fault Relay, System Log, and SMTP Email
Alert.

The following web pages are included in this group:

Fault Relay

Event Selection

on Page 112

SysLog Configuration

on Page 113

SMTP Configuration

on Page 114

Optionally, you can use the CLI for configuration, see

Warnings (CLI)

on Page 174.

Fault Relay

The ES8510-XTE provides 2 digital outputs (also called relay outputs). The
relay contacts are energized (open) for normal operation and closes under
fault conditions. Fault conditions include Digital Input (DI) State, Dry Output,
Power Failure, Link Failure, Ping Failure, and Super Ring Failure. You can
configure these settings in this Fault Relay Setting. Each Relay can be assigned
one fault condition.

Relay 1: Click the check box for Relay 1 then select the Event Type and its
parameters.

Relay 2: Click the check box for Relay 2 then select the Event Type and its
parameters.

Event Type: Includes DI State, Dry Output, Power Failure, Link Failure, Ping
Failure
, and Super Ring Failure. Each event type has its own parameters of
which you need to configure. Currently each relay can have one event type.

Event Type: DI State

DI Number: Select DI 1 or DI 2 to determine which DI you want to monitor.

DI State: Select whether you want to an event thrown when the voltage on
the DI is High or Low.

How to configure: Select the DI number and DI State you want to monitor. For example when DI 1 and High
are selected it means when DI 1’s voltage high the system shorts the relay output and light the DO LED.