Basic 32 Loader Control UGC007/0702

Fault Messages and Error Codes D-3

0006

MEMORY MODULE
HARDWARE FAULT

The memory module hardware
faulted or the memory module is
incompatible with OS.

Non-User

Upgrade the OS to be compatible with
memory module.

Obtain a new memory module.

0007

MEMORY MODULE
TRANSFER ERROR

Failure during memory module
transfer.

Non-User

Re-attempt the transfer. If the error persists,
replace the memory module.

0008

FATAL INTERNAL
SOFTWARE ERROR

An unexpected software error
occurred.

Non-User

Cycle power on your unit. Then,
re-download your program and re-initialize
any necessary data.

Start up your system.

Refer to proper grounding guidelines and
using surge suppressors in your controller’s
User Manual.

Contact your Conair Service

representative if the error persists.

0009

FATAL INTERNAL
HARDWARE ERROR

An unexpected hardware error
occurred.

Non-User

Cycle power on your unit. Then,
re-download your program and re-initialize
any necessary data.

Start up your system.

Refer to proper grounding guidelines and
using surge suppressors in your controller’s
User Manual.

Contact your Conair Service

representative if the error persists.

000A

OS MISSING OR
CORRUPT

The operating system required for
the user program is corrupt or
missing.

Non-User

Download a new OS using ControlFlash.

Contact your local Rockwell Automation
representative for more information about
available operating systems your
controller.

000B

BASE HARDWARE
FAULT

The base hardware faulted or is
incompatible with the OS.

Non-User

Upgrade the OS using ControlFlash.

Replace the Controller (MicroLogix 1200
only)
.

Replace the Base Unit (MicroLogix 1500
only)
.

Contact your Conair Service

representative for more information about
available operating systems your
controller.

0011

EXECUTABLE FILE 2 IS
MISSING

Ladder File 2 is missing from the
program.

Non-User

Re-compile and reload the program.

0012

LADDER PROGRAM
ERROR

The ladder program has a memory
integrity problem.

Non-User

Reload the program or re-compile and
reload the program. If the error persists, be
sure to use RSI programming software to
develop and load the program.

Refer to proper grounding guidelines and
using surge suppressors in your controller’s
User Manual.

0015

I/O CONFIGURATION
FILE ERROR

The user program I/O configuration
is invalid.

Non-User

Re-compile and reload the program, and enter
the Run mode. If the error persists, be sure to
use RSI programming software to develop
and load the program.

Error
Code
(Hex)

Advisory Message

Description

Fault
Classification

Recommended Action