Basic 32 Loader Control UGC007/0702

D-8 Fault Messages and Error Codes

xx8B

(1)(2)

EXPANSION I/O
POWER SUPPLY
CONFIGURATION
MISMATCH ERROR

Either an expansion I/O power
supply is configured in the user
program, but no power supply is
present, or

an expansion I/O power supply is
configured in the user program
and a power supply is physically
present, but the types do not
match.

Non-User

Correct the user program to eliminate a
power supply that is not present

Re-compile, reload the program and enter
the Run mode, or

With power removed, add the missing
power supply.

xx8C

(1)(2)

EXPANSION I/O
OBJECT TYPE
MISMATCH

An expansion I/O object (i.e. cable,
power supply, or module) in the user
program I/O configuration is not the
same object type as is physically
present.

Non-User

Correct the user program I/O configuration
so that the object types match the actual
configuration, and

Re-compile, reload the program and enter
the Run mode. Or

Correct the actual configuration to match
the user program I/O configuration.

Cycle power.

0x1F39

INVALID STRING
LENGTH

(3)

The first word of string data contains
a negative, zero, or value greater
than 82.

Recoverable

Check the first word of the string data
element for invalid values and correct the
data.

(1) xx indicates module number. If xx = 0, problem cannot be traced to a specific module.

(2) The xx in this error code means that the error occurs at the location of the last properly configured Expansion I/O module +1. You should use this information in conjunction

with the specific error code to determine the source of the problem.

(3) Applies to MicroLogix 1500 1764-LSP Series B and 1764-LRP Processors.

Error
Code
(Hex)

Advisory Message

Description

Fault
Classification

Recommended Action