Basic 32 Loader Control UGC007/0702

Fault Messages and Error Codes D-5

0028

INVALID OR
NONEXISTENT USER
FAULT ROUTINE
VALUE

A fault routine number was
entered in the status file, number
(S:29), but either the fault routine
was not physically created, or

the fault routine number was less
than 3 or greater than 255.

Non-User

Either clear the fault routine file number
(S:29) in the status file, or

create a fault routine for the file number
reference in the status file (S:29). The file
number must be greater than 2 and less
than 256.

0029

INSTRUCTION
INDIRECTION
OUTSIDE OF DATA
SPACE

An indirect address reference in the
ladder program is outside of the
entire data file space.

Recoverable

Correct the program to ensure that there are
no indirect references outside data file space.
Re-compile, reload the program and enter the
Run mode.

002E

EII ERROR

An error occurred in the EII
configuration.

Recoverable

See the Error Code in the EII Function File for
the specific error.

0030

SUBROUTINE
NESTING EXCEEDS
LIMIT

The JSR instruction nesting level
exceeded the controller memory
space.

Non-User

Correct the user program to reduce the
nesting levels used and to meet the
restrictions for the JSR instruction. Then
reload the program and Run.

0031

UNSUPPORTED
INSTRUCTION
DETECTED

The program contains an
instruction(s) that is not supported
by the controller.

Non-User

Modify the program so that all instructions
are supported by the controller.

Re-compile and reload the program and
enter the Run mode.

0032

SQO/SQC/SQL
OUTSIDE OF DATA
FILE SPACE

A sequencer instruction length/
position parameter references
outside of the entire data file space.

Recoverable

Correct the program to ensure that the
length and position parameters do not
point outside data file space.

Re-compile, reload the program and enter
the Run mode.

0033

BSL/BSR/FFL/FFU/LFL/
LFU CROSSED DATA
FILE SPACE

The length/position parameter of a
BSL, BSR, FFL, FFU, LFL, or LFU
instruction references outside of the
entire data file space.

Recoverable

Correct the program to ensure that the
length and position parameters do not
point outside of the data space.

Re-compile, reload the program and enter
the Run mode.

0034

NEGATIVE VALUE IN
TIMER PRESET OR
ACCUMULATOR

A negative value was loaded to a
timer preset or accumulator.

Recoverable

If the program is moving values to the
accumulated or preset word of a timer,
make certain these values are not
negative.

Reload the program and enter the Run
mode.

0035

ILLEGAL
INSTRUCTION IN
INTERRUPT FILE

The program contains a Temporary
End (TND), Refresh (REF), or Service
Communication instruction in an
interrupt subroutine (STI, EII, HSC) or
user fault routine.

Non-Recoverable

Correct the program.

Re-compile, reload the program and enter
the Run mode.

0036

INVALID PID
PARAMETER

An invalid value is being used for a
PID instruction parameter.

Recoverable Process Control Instruction for

more information about the PID instruction.

0037

HSC ERROR

An error occurred in the HSC
configuration.

Recoverable

See the Error Code in the HSC Function File
for the specific error.

003B

PTO ERROR

An error occurred in the PTO
instruction configuration.

Recoverable or
Non-User

See the Error Code in the PTO Function File for
the specific error.

003C

PWM ERROR

An error occurred in the PWM
instruction configuration.

Recoverable or
Non-User

See the Error Code in the PWM Function File
for the specific error.

Error
Code
(Hex)

Advisory Message

Description

Fault
Classification

Recommended Action