D-6 Fault Messages and Error Codes

003D

INVALID SEQUENCER
LENGTH/POSITION

A sequencer instruction (SQO, SQC,
SQL) length/position parameter is
greater than 255.

Recoverable

Correct the user program, then re-compile,
reload the program and enter the Run mode.

003E

INVALID BIT SHIFT OR
LIFO/FIFO
PARAMETER

A BSR or BSL instruction length
parameter is greater than 2048 or an
FFU, FFL, LFU, LFL instruction length
parameter is greater than 128 (word
file) or greater than 64 (double word
file)

Recoverable

Correct the user program or allocate more
data file space using the memory map, then
reload and Run.

003F

COP/FLL OUTSIDE OF
DATA FILE SPACE

A COP or FLL instruction length
parameter references outside of the
entire data space.

Recoverable

Correct the program to ensure that the
length and parameter do not point outside
of the data file space.

Re-compile, reload the program and enter
the Run mode.

0050

CONTROLLER TYPE
MISMATCH

A particular controller type was
selected in the user program
configuration, but did not match the
actual controller type.

Non-User

Connect to the hardware that is specified
in the user program, or

Reconfigure the program to match the
attached hardware.

0051

BASE TYPE
MISMATCH

A particular hardware type (AWA,
BWA, BXB) was selected in the user
program configuration, but did no
match the actual base.

Non-User

Connect to the hardware that is specified
in the user program, or

Reconfigure the program to match the
attached hardware.

0052

MINIMUM SERIES
ERROR

The hardware minimum series
selected in the user program
configuration was greater than the
series on the actual hardware.

Non-User

Connect to the hardware that is specified
in the user program, or

Reconfigure the program to match the
attached hardware.

0070

EXPANSION I/O
TERMINATOR
REMOVED
(MicroLogix 1500 only)

The required expansion I/O
terminator was removed.

Non-Recoverable

Check the expansion I/O terminator on the
last
I/O module.

Cycle power.

xx71

(1)

EXPANSION I/O
HARDWARE ERROR

The controller cannot communicate
with an expansion I/O module.

Non-Recoverable

Check connections.

Check for a noise problem and be sure
proper grounding practices are used.

Replace the module.

Cycle power.

xx79

(1)

EXPANSION I/O
MODULE ERROR

An expansion I/O module generated
an error.

Non-Recoverable

Refer to the I/O Module Status (IOS) file.

Consult the documentation for your
specific I/O module to determine possible
causes of a module error.

0080

EXPANSION I/O
TERMINATOR
REMOVED
(MicroLogix 1500 only)

The required expansion I/O
terminator was removed.

Non-User

Check expansion I/O terminator on last I/O
module.

Cycle power.

xx81

(1)

EXPANSION I/O
HARDWARE ERROR

The controller cannot communicate
with an expansion I/O module.

Non-User

Check connections.

Check for a noise problem and be sure
proper grounding practices are used.

Replace the module.

Cycle power.

Error
Code
(Hex)

Advisory Message

Description

Fault
Classification

Recommended Action