LAARS Sequencing Controls S8 & S8EXT

• In Cooling applications, the system relay will energize when the outdoor temperature is above the Outdoor Cutoff setting.

• A typical use of the SYS output is to activate a system pump starter. The pump can run whenever there is a call for heat/cool.

When stages are no longer required, the pump will stay active for an adjustable Run-On delay.

System Output Operation in Reset Mode

• The SYS output relay will energize whenever the outdoor temperature is below the Outdoor Cutoff.

• The SYS will remain constantly energized while the outdoor temperature is below the Outdoor Cutoff.

• When the outdoor temperature rises 2°F above the Outdoor Cutoff, the SYS output will remain energized for the period set by

the System Run-On.

• The SYS output has one Normally Open (N.O.) relay that acts as a dry contact only. It does not source any power.

• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

WIRING THE DHW PUMP (TERMINALS 21, 22)

The S8 can control the DHW Pump when the DHW Pump Output option is activated in the Startup Menu..

• The S8 will energize the DHW Pump whenever there is a call for DHW using a dry contact or when the DHW

temp falls below the DHW Set Point and DHW Differential.

• The DHW Pump output is Normally Open (N.O.) dry contact only. It does not source any power.

• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Setback Dry Contact

Lo Hi

Unit1

Stages

Lo Hi

Unit2

Stages

WIRING THE COMBUSTION AIR DAMPER (TERMINALS 23, 24)

The S8 can control the Combustion Air Damper when the Comb. Air Output option is activated in the Startup

Menu.

• The S8 will energize the Combustion Air Damper relay whenever there is a call to energize any of the unit

stages.

• The Comb. Air output has one Normally Open (N.O.) dry contact relay. It does not source any power.

• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

• In this scenario, the Prove input will be used to check on the Combustion Air Damper status.

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Setback Dry Contact

Lo Hi

Unit1

Stages

Lo Hi

Unit2

Stages

WIRING THE STAGES (TERMINALS 3 TO 17)

The S8 can be configured to operate the stages of the heating or cooling units. Moreover, it can be

configured to operate the unit pumps or valves in addition to the unit stages.

• The N.O. contacts are dry contacts only. They do not source any voltage.

• Wire the N.O. relay contacts in series with the unit’s limit circuit.

• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage

wiring.

WIRING THE STAGE OUTPUTS

• Each Stage output (A through H) has one Normally Open (N.O.) relay contact.

• When wiring several multi-stage units, start with the lower stage of the first unit and wire it to

Output A, followed by the higher stage of the same unit and wire it to Stage B.

WIRING THE PUMP OR VALVE OUTPUTS

• If the S8 is configured to operate Stage Pumps or Valves, then, wire them using the stage after the

highest stage for that unit. That is, the low stage for the first unit must be connected to A and the

higher stage of the same unit must be connected to Stage B. The Valve or Pump for the same unit

must be connected to Stage C.

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Setback Dry Contact

Lo Hi

Unit1

Stages

Lo Hi

Unit2

Stages

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.