CONNECTING TO THE S8EXT PANELS AND XSIG INTERFACE

• The S8 is equipped with a 6-pin phone socket to connect to S8EXT panels or XSIG Interface.

• Only 6-wire phone cable provided must be used for proper operation.

• Each S8 Extension has two RS485 communication ports. Use one to connect to the S8. Use the other port to connect to the

second extension or XSIG Interface.

• Additional compatible devices can utilize the second RS485 connection on the second S8 Extension. i.e. XSIG Interface

(CA004200) to provide a 4-20mA set point signal to the S8.

SELECTING THE S8EXT PANEL LETTER

• The S8 is capable of communicating to two S8EXTs. However, each extension must be identified

as either A or B using the switch on each extension to avoid having communication problem.

• Extension A (Switch is set to "A") will operate stages "I" through "P". While Extension B

(Switch is set to "B") will operate stages "Q" through "X".

Connecting S8 to Two Extension Panels

and XSIG Interface using RS485

S8

SYSTEM

DHW PUMP

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

SYS=

144

F OD=

35

F

<AB > DE

GH

JK

HI LO -- OFF

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

STAGE

MENU

Stage E

Stage F

Stage G

Stage H

Stage A

Stage B

Stage C

Stage D

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

COMB. AIR

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT A

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT B

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

4-20 mA EMS

4-20mA INPUT

+

Signal GND

1

2

3

RS485

EXTENSION

CONNECTORS

XSIG 4-20mA EMS Interface

4-20mA

EMS Signal

(+)

(-)

6 Pin Phone Cable (provided with Extension)

6 Pin Phone Cable (provided with XSIG Interface)

S8

SEQUENCING CONTROL

S8EXT

SEQUENCING CONTROL

XSIG

Connecting S8 to Two Extension Panels

and XSIG Interface using RS485

S8

SYSTEM

DHW PUMP

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

SYS=

144

F OD=

35

F

<AB > DE

GH

JK

HI LO -- OFF

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

STAGE

MENU

Stage E

Stage F

Stage G

Stage H

Stage A

Stage B

Stage C

Stage D

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

COMB. AIR

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N
Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT A

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N
Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT B

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

4-20 mA EMS

4-20mA INPUT

+ Signal GND

1

2

3

RS485

EXTENSION

CONNECTORS

XSIG 4-20mA EMS Interface

4-20mA

EMS Signal

(+)

(-)

6 Pin Phone Cable (provided with Extension)

6 Pin Phone Cable (provided with XSIG Interface)

S8

SEQUENCING CONTROL

S8EXT

SEQUENCING CONTROL

XSIG