LAARS Sequencing Controls S8 & S8EXT

WIRING

WIRING THE POWER (TERMINALS 1, 2)

• Bring the 120VAC 60Hz power wires through the bottom Knockout of the enclosure.

• Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

• Connect the hot line to terminal marked L.

• Connect the neutral line to the terminal marked N.

WARNING

Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage

wiring. Laars recommends installing a surge suppressor on the power source to the S8.

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Setback Dry Contact

Lo Hi

Unit1

Stages

Lo Hi

Unit2

Stages

WARNING

Connect the shield at the control terminal end and cut the shield wire at the sensor end.

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Setback Dry Contact

Lo Hi

Unit1

Stages

Lo Hi

Unit2

Stages

WIRING THE SENSORS

SYSTEM TEMPERATURE SENSOR WIRING (TERMINALS 27, 28)

• A S8 must be connected to a temperature sensor located in the common header.

• The S8 is designed to be connected to a temperature sensor (CA002400 or equivalent) for immersion in a

3/8ID well (CA002500 or equivalent). Contact the factory for additional temperature sensor options.

• Temperature sensor wires can be extended up to 500’ by splicing shielded 2-

conductor cable (Belden #8760 or equivalent).

• Temperature sensors have no polarity. Connect the two wires from the

sensor to the S8 terminals marked SYSTEM TEMP 27, 28.

• Connect the sensor shield to the circled terminal 28 with one of the sensor wires.

OUTDOOR SENSOR WIRING (TERMINALS 29, 30)

• When Outdoor Reset is selected, the S8 will vary the system Set Point based on outdoor temperature.

• Whether in Set Point or Outdoor Reset modes, the outdoor sensor can be used as an Outdoor Cutoff. In

heating, the S8 will disable all Boilers when the outdoor temperature is above the adjustable Outdoor

Cutoff temperature. However, in cooling it will disable the units when the outdoor temperature is below

the Outdoor Cutoff. This feature will automatically be activated when an outdoor sensor is connected.

• For an outdoor sensor use a Laars outdoor sensor (CA002400 or equivalent).

• The sensor wires can be extended up to 500’ using shielded 2-conductor cable (Belden #8760 or equivalent).

• Temperature sensors have no polarity. Connect the wires from the outdoor

sensor to the S8 terminals marked OUTDOOR TEMP - 29, 30.

• Connect the shield to the circled terminal 30 with one of the sensor wires.

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Setback Dry Contact

Lo Hi

Unit1

Stages

Lo Hi

Unit2

Stages

RETURN SENSOR WIRING (TERMINALS 31, 32) OPTIONAL (AVAILABLE IN HEATING ONLY)

• If the Return Sensor is connected, must be purchased separately, the S8 will recognize

it and alternate its temperature on the display with the Target temperature. If the Return

is below the Minimum Return, the S8 will sequence stages based on the Return Sensor,

Minimum Return, Calculated Target, and the actual System Temperature.

• The Return on the S8 is designed to be connected to a temperature sensor that can be purchased

separately (CA002400 or equivalent) for immersion in a 3/8ID well (CA002500 or equivalent).

• The sensor wires can be extended up to 500’ using shielded 2-conductor cable (Belden #8760 or equivalent).

• Temperature sensors have no polarity. Connect the wires from the outdoor

sensor to the S8 terminals marked OUTDOOR TEMP - 31, 32.

• Connect the shield to the circled terminal 32 with one of the sensor wires.

Line

Neutral

120VAC

Power Source

Sensor Shiled

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Outdoor Sensor

Prove Dry Contact

Sensor Shiled

System Sensor

Sensor Shiled

Return Sensor

Shutdown Dry Contact

Sensor Shiled

DHW Sensor

Lo Hi

Unit1

Stages

Unit1

Pump

Lo Hi

Unit2

Stages

Unit2

Pump

System

Pump

DHW

Pump

Comb.

Air

Damper

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC.

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

Setback Dry Contact

Lo Hi

Unit1

Stages

Lo Hi

Unit2

Stages