LAARS S8Ext - Installation Manual User Manual

Page 13

Advertising
background image

Page 13

LAARS Sequencing Controls S8 & S8EXT

----- SETTINGS ------

Season

Winter

<Outdoor Rst>

135 F

Set Point

140 F

EMS Set Point

135 F

Min Return

110 F

<System Settings>

<Maintenance>

<System Startup>

BACK SELECT

---- SEASON ---

Winter

Summer

BACK SAVE

-- OUTDOOR RESET -

Reset Ratio

7

Target Offset +0 F

Outdoor Cutoff

65 F

Min.Target

120 F

Max.Target

120 F

BACK SELECT

---- RESET RATIO ---

Custom
1(8.00 OD:1.00 SYS)
2(4.00 OD:1.00 SYS)
3(3.00 OD:1.00 SYS)
4(2.00 OD:1.00 SYS)
5(1.50 OD:1.00 SYS)
6(1.25 OD:1.00 SYS)

7(1.00 OD:1.00 SYS)

8(1.00 OD:1.25 SYS)
9(1.00 OD:1.50 SYS)
10(1.00 OD:2.00 SYS)
11(1.00 OD:3.00 SYS)
12(1.00 OD:4.00 SYS)

BACK SAVE

-- SET SYS TEMP.1 -

100 F

[

]

BACK SAVE

-- AT OD TEMP.1 ---

70 F

[

]

BACK SAVE

-- SET SYS TEMP.2 -

170 F

[

]

BACK SAVE

-- AT OD TEMP.2 ---

0 F

[ ]

BACK SAVE

-- TARGET OFFSET ---

+0 F

[

]

BACK SAVE

-- OUTDOOR CUTOFF --

70 F

[

]

BACK SAVE

---- MIN TARGET ----

120 F

[

]

BACK SAVE

---- MAX TARGET ----

240 F

[

]

BACK SAVE

----- SET POINT -----

140 F

[

]

BACK SAVE

-- EMS SET POINT --

140 F

BACK SAVE

- SYSTEM SETTINGS -

<Stage Settings>

<Setback Schedule>

<DHW Settings>

Setback

0 F

Run-On

2min

Pump Exercise Off

BACK SELECT

---- MIN RETURN ----

120 F

[

]

BACK SAVE

---- RETURN LAG ----

2min

[

]

BACK SAVE

--- PUMP EXERCISE --

Off

On

BACK SAVE

------- RUN-ON -------

2min

[

]

BACK SAVE

------ SETBACK -------

0 F

[ ]

BACK SAVE

-- DHW SETTINGS ---

DHW Temp.

120 F

DHW Prior Tmr

60min

DHW Set Point

120 F

DHW Diff.

5 F

BACK SELECT

DHW PRIORITY TIMER

2min

[ ]

BACK SAVE

-- DHW SET POINT --

120 F

[

]

BACK SAVE

DHW DIFFERENTIAL

10 F

[

]

BACK SAVE

SYS=

168

F OD=

45

F

TGT=172 F

ABC <EFG >

---- LO

BOILER MENU

DHW SETTINGS

RESET RATIO

SET POINT