LAARS Sequencing Controls S8 & S8EXT

AUTOMATIC ROTATION AMONG BOILERS

• Rotating the lead unit to be activated on a call for output promotes even wear on all units. The S8 has three modes of rotation: Manual,

First-On-First-Off, or Timed Rotation. This option automatically rotates units every selected time period from one hour to every

41(999 hours) days.

SETBACK OR DAY/NIGHT SCHEDULING

Two Setback modes are available for the S8:

• The Day/Night Scheduling provides an adjustable time-based schedule for the Setback.

• The Setback mode uses an external signal to switch the operation of the S8 in and out of setback mode.

INSTALLATION

Each of the S8 or S8EXT consists of three primary enclosure components.

• The Enclosure Display Module: contains the display, buttons, LEDs

and electric wiring terminals. It has two screws to hold it to the base. A

program configuration switch, used to adjust S8 settings, is placed above

the terminals. This switch is enclosed with the enclosure wiring cover for

security. Wiring terminals are of the plug-in type to ease installation and

removal.

• The Enclosure Base: contains the holes to mount and hold the control

against the wall or any flat surface. All other enclosure components mount

on the base. The bottom section of the Enclosure Base contains the wiring

chamber with knockouts on the bottom to easy installation.

• The Enclosure Wiring Cover: seals the wires from the external

environment. It has two screws to hold it the base and a hole to secure

a lock on the wiring enclosure. A plastic web that separates the wiring

chamber into high and low volt sections has been provided.

MOUNTING THE ENCLOSURE

• Select a location near the equipment to be controlled.

• The surface should be flat, and be sufficiently wide and strong to hold the

S8 or S8EXT.

• Keep the control away from extreme heat, cold, or humidity. Ambient

operating temperature is from 20 to 120°F.

• Remove the Enclosure Wiring Cover from the control enclosure by

removing the two bottom screws.

• Remove the Enclosure Display Module by removing the middle screws.

• Screw the Enclosure Base to the surface through the upper and lower

mounting holes on the back of the enclosure.

• Replace the Enclosure Display Module and replace the middle screws.

• Do not replace the enclosure wiring cover until all wiring is done.

• When purchasing a padlock for the enclosure, the maximum shank diameter

should not exceed ¼"