LAARS S8Ext - Installation Manual User Manual

Page 18

Advertising
background image

Page 18

LAARS Heating Systems

BURNER TYPE

On/Off, 2-Stage, 3-Stage, 4-Stage

Default: On/Off

Button: MENU/<System Startup>/..../Burner Type

• The S8 can sequence from a single stage and up to four stages per heating or cooling

unit.

--- BURNER TYPE ----

On/Off

2-Stage

3-Stage

4-Stage

BACK SAVE

BOILER OUTPUT

None, Pump, Valve

Default: None

Button: MENU/<System Startup>/..../Boiler Output

• When None is selected, the S8 will sequence multiple heating or cooling units without

any additional unit pumps or valves.

• The Pump option allows the S8 to control the cooling or heating unit stages in addition

to the unit pumps. The stage pump will run for the Run-On delay after the lower stage of

that unit has de-energized.

-- BOILER OUTPUT --

None

Pump

Valve

BACK SAVE

• The Valve optional functions similar to the pump option except that when all stages are off and after Run-On delay has elapsed,

the Lead unit's valve relay will remain energized to allow for pump flow across the system. The lead unit's valve will remain

energized until the Outdoor temperature rises above the Outdoor Cutoff or when the Shutdown, or Summer is activated.

TOTAL BOILERS

1 to 24

Default: varies based on Burner Type and Boiler Output

Button: MENU/<System Startup>/..../Boiler Output

• This option in combination with Burner Type and Boiler Output Startup options will

determine the total number of outputs the S8 will need to control.

• If more stages are selected than the S8 and S8 Extension has, the extra stages will have

CE as their status.

-- TOTAL BOILERS --

8

[

]

BACK SAVE

STAGING

Multiple Outputs, Single Output

Default: Multiple Outputs

Button: MENU/<System Startup>/..../Staging

• Most units will require that the higher output stages to be energized after the lower output

stages. These units will need to select the Multiple Output option. That means, both

Low and High Output stages must be energized for the unit to function.

• Some units require that when the higher output stages are required, the lower stages must

de-energize. To operate these units, the user must select the Single Output option.

------ STAGING ------

Multiple Outputs

Single Output

BACK SAVE

SEQUENCE

Lo/Hi/Lo/Hi, Lo/Lo/Hi/Hi

Default: Lo/Hi/Lo/Hi

Button: MENU/<System Startup>/..../Sequencing

• Some units run more efficient when the lower stages are energized alone than with

the higher stages. These types of units should select Lo/Lo/Hi/Hi. Then, the S8 will

sequence the lower stages of all Automatic units before sequencing the higher stages.

------ SEQUENCE -------

Lo/Hi/Lo/Hi

Lo/Lo/Hi/Hi

BACK SAVE

• For

stage of the same unit. Then when more stages are needed, it will fire the lower stage of the lag unit followed by the higher

stage of the lag unit.

CONTROL LOGIC

PID, OSS (Over-Sized-System)

Default: PID

Button: MENU/<System Startup>/..../Sequencing

• The PID option allows the S8 to sequence stages based on Reaction Time and Boiler Min

Run Time. The PID relies on the rate of change in the System Temperature. The PID

logarithmic calculations foresee changes and sequence stages based on those changes. It

is the most efficient operation for most heating and cooling applications.

--- CONTROL LOGIC---

PID

OSS

BACK SAVE

Advertising
This manual is related to the following products: