LAARS Sequencing Controls S8 & S8EXT

APPLICATION

Heating-BreakOnRise, Cooling-MakeOnRise

Default: Heating-BreakOnRise

Button: MENU/<System Startup>/..../Application

• The S8 offers two application modes, Heating and Cooling. In Heating, the S8 will

sequence stages and when the system temperature is below the set point. In addition,

the system relay will energize when the outdoor temperature is at or below the Outdoor

Cutoff setting.

---- APPLICATION ---

Heat-BreakOnRise

Cool-MakeOnRise

BACK SAVE

• In Cooling, the S8 will sequence stages and when the system temperature is above the set point. In addition, the system relay

will energize when the outdoor temperature is at or above the Outdoor Cutoff setting.

• No Return Temperature monitoring or DHW options will be available in cooling applications.

DHW PIPING (AVAILABLE WITH HEATING ONLY)

Parallel, Primary/Secondary

Default: Parallel

Button: MENU/<System Startup>/..../DHW Piping

• When Parallel is selected, the S8 will offer a DHW Priority Timer. The DHW Priority

will only take place during heating periods.

• The Parallel option will allow the DHW Pump relay to energize while de-energizing the

System relay when there is a DHW call during heating. However, during Summer, only

the DHW Pump relay will energize on a DHW call.

---- DHW PIPING ---

Parallel

Primary/Secondary

BACK SAVE

• Selecting the Primary/Secondary option will energize the System relay with the DHW Pump relay whenever there is a call for

DHW even during the Summer or when outdoor temperature is above the Outdoor Cutoff.

IMPORTANT

A DHW call can be initiated by either a dry contact or using a Laars Sensor (CA002400 or

equivalent) for immersion in a 3/8ID well (CA002500 or equivalent). The use of a sensor will allow

the adjustment of DHW Set Point and DHW Differential.

DHW PUMP OUTPUT

No, Yes

Default: No

Button: MENU/<System Startup>/..../DHW Pump Output

• The S8 can control the operation of the DHW Pump. This option allows the user to

select if the S8 should be controlling the DHW Pump or not.

--DHW PUMP OUTPUT--

No

Yes

BACK SAVE

COMBUSTION AIR DAMPER OUTPUT

No, Yes

Default: No

Button: MENU/<System Startup>/..../Comb. Air Output

• The S8 can control the operation of the Combustion Air Damper. This option allows the

user to select if the S8 should be controlling the Combustion Air Damper or not.

- COMB. AIR OUTPUT-

No

Yes

BACK SAVE

• If Yes is selected, the S8 will energize the Comb. Air relay whenever there is a call for a boiler and will use the Prove input to

check on the status of the Combustion Air Damper. In a failure situation, the message "Wait for Comb. Prove"

will display when there is a call for a boiler stage until Prove is Shorted.

• If Prove fails after boiler stages where energized, the stages will de-energize and the message "Comb. Prove

Failure" will display until situation is rectified.

• If No is selected, the Prove input will be used to check System status instead of the Combustion Air Damper.

SETBACK MODE

Day/Night Schedules, External Signal

Default: Day/Night Schedules

Button: MENU/<System Startup>/..../Setback Mode

• The S8 can either utilize its built-in day schedule or an external dry contact signal to

switch to Setback.

--- SETBACK MODE --

Day/Night Schedule

External Signal

BACK SAVE

• If Day/Night Schedules is selected, The Setback will follow the Day/Night Schedule and Shutdown/Setback input (terminals 35

and 36) will be used as Shutdown only.

• The External Signal will allow the Shutdown/Setback input (terminals 35 and 36) to work as an input for Setback. No

Shutdown input will be available in this scenario.