LAARS Heating Systems

• Holding Return at 110˚F The Return sensor is reading less than the Minimum Return. S8 is trying to raise return to 110˚F.

• Holding Until 150˚F

The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when

system temperature reaches 150˚F.

• Waiting for Comb. Prove The System or Combustion Air Damper relay is ON and the prove terminals are open before the lead

boiler relay can energize.

• SYS Prove Failure

After boilers have run for a while, Prove signal was opened. The boiler relays will de-energize.

However, the System relay will remain energized.

STAGE SETTINGS

Button: BOILER/

• In most installations, all active unit adjustments are the same, but each can be configured

differently if desired.

• When the BOILER or C.UNIT button is depressed, the Unit A Settings menu will be

shown.

• Make all the appropriate settings for Unit A (See below).

• Then select the Next Stage option from the menu to bring up the Boiler B Settings menu

and make all the settings. Continue until all boilers have been set.

• If a S8EXT is connected to the S8, scrolling through stages using the Next and Prev

Stage menu options will scroll through the S8EXT stages as well.

CAUTION

To be able to change the S8 settings, the Program/Run Switch must be set to

Program. The switch is located under the Enclosure Wiring Cover for security.

The Enclosure Wiring Cover can be securely closed using a padlock.

----- BOILER AB -----

Mode

Auto

Runtime

58Hrs

<Prev Boiler>

<Next Boiler>

BACK SAVE

Connecting S8 to Two Extension Panels

and XSIG Interface using RS485

S8

SYSTEM

DHW PUMP

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

SYS=

144

F OD=

35

F

<AB > DE

GH

JK

HI LO -- OFF

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

STAGE

MENU

Stage E

Stage F

Stage G

Stage H

Stage A

Stage B

Stage C

Stage D

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

COMB. AIR

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT A

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT B

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

4-20 mA EMS

4-20mA INPUT

+

Signal GND

1

2

3

RS485

EXTENSION

CONNECTORS

XSIG 4-20mA EMS Interface

4-20mA

EMS Signal

(+)

(-)

6 Pin Phone Cable (provided with Extension)

6 Pin Phone Cable (provided with XSIG Interface)

S8

SEQUENCING CONTROL

S8EXT

SEQUENCING CONTROL

XSIG

MODE

Auto, Standby, Off, On

Default: Auto

Button: BOILER/Mode

• The S8 only controls any unit set to Auto or (after a delay) those set to Standby. None of

the other settings is recommended for output units connected to active units.

• Any output without an active unit connected must be set to Off.

• The following list describes the MODE options:

-- BOILER AB MODE -

Auto

Standby

Off

On

BACK SAVE

Auto - The S8 will control the unit’s operation to maintain the desired Set Point. Only units set to Auto can be Lead.

Standby Standby units can only be activated when all units in Auto have been at HI for an adjustable Standby delay period.

Standby is generally used when you want a specific unit to be available in extreme load conditions. Note that a Standby

unit Cannot be a Lead unit. Standby Time is only available in PID mode.

Off

Any output unit A through D not connected to a physical unit should be set to Off. The Off Mode can also be used to

disable units that are being serviced. The number of units and their stages are selected in the Startup menu.

On

The On Mode should only be used when testing a unit. The On Mode overrides the PROVE input. Once set to On the unit

will immediately start all of its stages.

RUNTIME

Clear

Button: BOILER/RunTime

• The RunTime provides an accumulative hourly run for the selected unit.

• The RunTime for a specific unit can be reset to zero by pressing the middle two buttons.

BOILER AB RUNTIME

58hrs

BACK CLEAR OK