LAARS Heating Systems

OPERATING SETTINGS

PROGRAM CHANGE SETTINGS

To be able to change the S8 settings the Program/Run Switch must be set to Program. The

switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover

can be securely closed using a padlock.

Connecting S8 to Two Extension Panels

and XSIG Interface using RS485

S8

SYSTEM

DHW PUMP

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

SYS=

144

F OD=

35

F

<AB > DE

GH

JK

HI LO -- OFF

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

STAGE

MENU

Stage E

Stage F

Stage G

Stage H

Stage A

Stage B

Stage C

Stage D

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

COMB. AIR

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT A

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT B

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

4-20 mA EMS

4-20mA INPUT

+

Signal GND

1

2

3

RS485

EXTENSION

CONNECTORS

XSIG 4-20mA EMS Interface

4-20mA

EMS Signal

(+)

(-)

6 Pin Phone Cable (provided with Extension)

6 Pin Phone Cable (provided with XSIG Interface)

S8

SEQUENCING CONTROL

S8EXT

SEQUENCING CONTROL

XSIG

CAUTION

DO NOT turn power off to the S8

when in off-season or season is

over. If you do so, the battery

will run down and will have to

be replaced. Instead switch to

Summer or Winter.

---- SEASON ---

Winter

Summer

BACK SAVE

SEASON

Winter, Summer

Default: Winter

Button: MENU/Season

• When in Summer, and in Heating Mode, the S8 will turn all boiler relays off. However,

a DHW call will bring boilers back on if needed. The Message Display Line will display
Summer. On ther other hand, in Cooling Mode, the S8 will turn all boiler relays off

when it is in Winter setting. The Message Display Line will show Winter.

• When in Winter, the S8 will activate the Sys relay whenever the Outdoor temperature

falls to or below the Outdoor Cutoff setting in heating applications. In addition, it will

begin heating whenever the System temperature falls below the Set Point Temperature.

The Message Display Line will not display any season information. However, in

Cooling , all stages will be off and the Message Display Line will display Winter.

• When the season is over, it is a good practice to switch the S8 Season setting. This will

allow DHW calls in heating to operate the boilers when needed.

RESET RATIO

Custom, 1(8.00ºOD : 1.00ºSys) to 12 (4.00ºOD : 1.00ºSys) Default: 1(1.00ºOD : 1.00ºSys)

Button: MENU/<Outdoor Reset>/Reset Ratio

In Outdoor Reset Only

• The Reset Ratio applies only to Heating applications.

• The Reset Ratio determines how the System water temperature will vary with Outside

temperature. With any of the ratios, the colder it becomes outside, the hotter the

temperature of the system water. (See Understanding Operation Concept on page 5)

• With a 1.00 (OD):4.00 (SYS) ratio, the System water temperature (SYS) will increase

rapidly as the outside temperature falls, hitting the Maximum of 240°F at 35°F outside

temperature. With a 4.00 (OD):1.00 (SYS) ratio, the System water temperature (SYS)

will increase slowly as the outside temperature falls. Even at -30°F, the system water

will only be 125°F, and at 22°F outside, the system water will be 112°F. Such a low

Reset Ratio might be used with radiant floor heating applications.

• With most baseboard heating applications, a 1.00 (OD):1.00 (SYS) setting is a good

place to start. With a 1.00 (OD):1.00 (SYS) ratio, for every degree the outside

temperature falls, the system water temperature is increased one degree.

---- RESET RATIO ---

Custom
1(8.00 OD:1.00 SYS)
2(4.00 OD:1.00 SYS)
3(3.00 OD:1.00 SYS)
4(2.00 OD:1.00 SYS)
5(1.50 OD:1.00 SYS)
6(1.25 OD:1.00 SYS)

7(1.00 OD:1.00 SYS)

8(1.00 OD:1.25 SYS)
9(1.00 OD:1.50 SYS)
10(1.00 OD:2.00 SYS)
11(1.00 OD:3.00 SYS)
12(1.00 OD:4.00 SYS)

BACK SAVE

• If required: Adjust the RESET RATIO in cold weather. If the ambient building

temperatures are too cold in cold weather, move the ratio to a higher selection. That is,

if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to 1.00 (OD):1.25

(SYS). If the building temperatures are too warm in cold weather, move the ratio to

a lower selection. That is, if 1.00 (OD):1.00 (SYS) was initially selected, change the

selection to 1.25 (OD):1.00 (SYS).

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

110

100

90

80

Outdoor Temperature

W

at

er

Te

m

pe

ra

tu

re

70

40

50

60

150

140

130

120

1:4

With a 0° Offset, the
ratio curves begin at
100° Water Temperature.

With a -20° Offset, the
ratio curves begin at
80° Water Temperature.

With a +20° Offset, the
ratio curves begin at
120° Water Temperature.

1:4

1:4

1:1

1:1

1:1

4:1

4:1

4:1

90

100

+20 Offset

-20 Offset

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

1:4

1:1

4:1

Colder

Warmer

CUSTOMIZED RESET RATIO

Button: MENU/<Outdoor Reset>/Reset Ratio/Custom

• F

can be used.

• The Custom Reset Ratio is only available when Custom is selected from the Reset Ratio menu option. It provides the user

with the capability of assigning two points on the reset ratio diagram and use the line that connects those two points as the

customized reset ratio curve. Each of the two points will need a specific System and Outdoor Temperature to identify it on the

diagram.