S8ext a, S8ext b, S8ext – LAARS S8Ext - Installation Manual User Manual

Page 23: Xsig, 20 ma ems, System settings, Stage settings, F od, F<ab > de gh jk hi lo -- off, Op power

Advertising
background image

Page 23

LAARS Sequencing Controls S8 & S8EXT

SYSTEM SETTINGS

Button: MENU/<System Settings>

The System Settings menu provide access to adjusting and fine-tuning the system for enhanced

comfort and better fuel savings. The S8 behaves differently based on the selected Control

Modes (see Startup Settings).

- SYSTEM SETTINGS -

BACK SELECT

Connecting S8 to Two Extension Panels

and XSIG Interface using RS485

S8

SYSTEM

DHW PUMP

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

SENSORS MUST BE GOLD SERIES

SYSTEM

3

DHW

PUMP

5

Stage A

7

Stage B

9

Stage C

11

13

Stage E

15

Stage F

17

Stage D

6

8

10

12

14

16

18

RS485

SYS=

144

F OD=

35

F

<AB > DE

GH

JK

HI LO -- OFF

4

Stage G

19

Stage H

21

OUTDOOR

TEMP

27

29

31

DHW

33

SHUTDOWN

/SETBACK

35

RETURN

TEMP

20

22

28

30

32

34

36

STAGE

MENU

Stage E

Stage F

Stage G

Stage H

Stage A

Stage B

Stage C

Stage D

25

26

PRESS

+ -

37

38

PROVE

SYSTEM

TEMP

PROGRAM

RUN

23 24

COMB.

AIR

DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS

COMB. AIR

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT A

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

O

P

Power

CAUTION:

Risk of Electric Shock.

PWR

L N
1 2

I

3 4

J

5 6

K

7 8

L

9 10

M

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

Ext B

L

M

N

Comm

T
U
V

W
X

N

13 14

Q

S

U

R

T

V

S8EXT B

Use Copper Conductors Only.

I

J

K

Q
R
S

O

15 16

P

17 18

W

X

4-20 mA EMS

4-20mA INPUT

+

Signal GND

1

2

3

RS485

EXTENSION

CONNECTORS

XSIG 4-20mA EMS Interface

4-20mA

EMS Signal

(+)

(-)

6 Pin Phone Cable (provided with Extension)

6 Pin Phone Cable (provided with XSIG Interface)

S8

SEQUENCING CONTROL

S8EXT

SEQUENCING CONTROL

XSIG

PROGRAM CHANGE SETTINGS

To be able to change the S8 settings the Program/Run Switch must be set to Program. The

switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring

Cover can be securely closed using a padlock.

STAGE SETTINGS

Button: MENU/<System Settings>/<Stage Settings>

-- STAGE SETTINGS --

BACK SELECT

-- REACTION TIME --

2min

BACK SAVE

REACTION TIME

Adjustable 1 - 10 minutes

Default: 2 minutes

Button: MENU/<System Settings>/<Stage Settings>/Reaction Time in PID Logic only

• It is the amount of time it takes a single stage to affect the system.

• After the S8 turns on a stage trying to meet a set point, it will not turn on another stage

until the reaction time has elapsed. Then, it will recalculate if a stage is need.

• To determine the optimum time, in a heating system start with a hot system. However,

in a cooling system start with a cool system. Then, turn on a single stage and calculate

how long it takes until the system begins to respond to that stage. That period should be

set as the Reaction Time.

PURGE DELAY

Adjustable 0.0 - 10.0 minutes

Default: 0.0 minutes

Button: MENU/<System Settings>/<Stage Settings>/Purge Delay

in PID Logic only

• Most large units must go through a purge cycle before they are brought on line.

• When the S8 activates a unit (the lowest stage on a unit), it does not start to calculate

its output until the Purge Delay is over. This allows the unit to fully come on line and to

begin producing output.

--- PURGE DELAY ----

0.0min

[ ]

BACK SAVE

• The Purge Delay helps to prevent short cycling of a newly activated units. Once the lowest unit stage is activated, it MUST run

through the entire Purge Delay period.

• The minimum Purge Delay setting MUST be set to the time required by the units manufacturer specification.

MINIMUM RUNTIME

Adjustable 1 - 60 minutes

Default: 2 minutes

Button: MENU/<System Settings>/<Stage Settings>/Min Runtime

in PID Logic only

• This is the minimum amount of time any stage will run.

• For the lowest stage of a unit, the Minimum Runtime starts after the purge cycle.

- MINIMUM RUNTIME -

2min

[

]

BACK SAVE

• Initially, set the Min Runtime to half the Reaction Time.

• If System tends to overshoot, reduce the Min Runtime. If boilers tends to short cycle, increase Min Runtime.

STANDBY DELAY

Adjustable 1 - 60 minutes

Default: 10 minutes

Button: MENU/<System Settings>/<Stage Settings>/Standby Delay in PID Logic only

• The Standby Delay Time only applies to units in Standby Mode.

• A Standby unit can only be activated after all the units in Auto Mode have run for the

full Standby Time.

-- STANDBY DELAY --

10min

[

]

BACK SAVE