SPECIFICATIONS:

Voltage Input:

. . . . . . . . .

120 VAC 60 Hz

Power Consumption:

. . . . . . .

12 VA Max

Operating Temperature:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

°

F/-7

°

C to 120

°

F/49

°

C

Operating Humidity:

. . . . . . .

20% to 80%

Dimensions:

. . . . . . . . .

11"W x 9" H x 3 ¾

Weight:

. . . . . . . . . . . . . . .

2.5 pounds

S8 Specifications:

Lead Stage Rotation:

. . . . . . . . . . . . . . . . . . . . . . . Time ( 1 to 999 Hours (41 days)), Manual, First-On/First-Off

S8 Outputs and LEDs:

. . . . . . . . . . . . . . . . 11 N.O. S.P.S.T (8 Stages, 1 System, 1 DHW Pump, 1 Combustion Air)

S8 Inputs:

. . . . . . . . . . . . . . . . . . 1 Sys(Temp), 1 Outdoor, Return Temp, DHW Temp, Ext Setback/Shutdown, Prove

Stage Modes:

. . . . . .

Auto, Standby, Off, On

Standby Time (PID only):

.

1 to 60 minutes

Output Relay Ratings:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Amp inductive at 120 VAC 60 Hz

Add-On S8EXT Panels:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up two S8EXT Panels using RS485

Temperature Display:

Fahrenheit or Celsius.

Display:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Graphical Alphanumeric (7 rows x 21 char. each)

Temperature Sensor Ranges:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -35

°

F/-37

°

C to 250

°

F/121

°

C

Outdoor Cutoff Range: . . . . . . . . . . . . . . . . . . . . . . . . . . .

20°F/-7°C to 100°F/38°C, ON and OFF

Set Point: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

-10°F/-23°C to 230°F/110°C

External Set Point: . . . . . . . . . . . . . . . . . . . .

-10°F/-23°C to 240°F/116°C using XSIG Interface (optional)

Reset Ratio Range (Outdoor Reset Only): . . . . . . (

8:1) to (1:4) (Outdoor : System Water), and Custom Reset Ratio

Offset Adjustment (Outdoor Reset Only):

. . . . . . . . . . . . . . . . . . . . . . . . -40°F/-22°C to plus 40°F/22°C

Minimum Target (Outdoor Reset Only): . . . . . . . . . . . . . . . . . . . . . . . .

70

°

F/21

°

C to 170

°

F/77

°

C

Maximum Target (Outdoor Reset Only): . . . . . . . . . . . . . . . . . . . . . . .

90

°

F/32

°

C to 240

°

F/116°C

Reaction Time (PID only): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 to 10 minutes

Minimum Run-Time (PID only): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 to 60 minutes

Purge Delay (PID only):

.

0.0 to 10.0 minutes

Last Stage Hold (PID only):

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°F/0°C to 30°F/17°C

Throttle Range (OSS only): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2°F/1°C to 20°F/11°C

Domestic Hot Water Priority Options:

. . . . . .Parallel Piping with Priority or without Priority and Primary Secondary

Pump Run-On:

. . . . . . . . .

0 to 60 minutes

Pump Exercise:

. . . . . . . . . . .

Yes or No

Schedules:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Day and 1 Night (Setback) settings per day

Night Setback:

. . . . .

0°F/0°C to 80°F/44°C

Power Backup:

. . . . . . . .Lithium coin battery, 100 days minimum 5 year replacement (Maintains Clock in power outages).

External Inputs:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shutdown Input, and Prove Input. (Dry Contacts Only)

Season:

. . . . . . . . . . .

Winter and Summer.

S8EXT Specifications:

Extension Numbering:

.

Toggle Switch A or B

LED:

. . . 1 Power (Dual Color Green (A)/Red (B)), 1 Communication, 8 Stage Output relays (Dual Color Green (A)/Red (B))

Stage Outputs:

. . . . . . . . .

8 N.O. S.P.S.T.

Output Relay Ratings:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Amp inductive at 120 VAC 60 Hz

Connection to S8 and another S8EXT:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two RS485