LAARS S8Ext - Installation Manual User Manual

Page 29

Advertising
background image

Page 29

LAARS Sequencing Controls S8 & S8EXT

• To view the values of specific time period, use the two middle buttons to scroll to that time and read the upper left temperature.

• The first screen will be the System Temperature History. By clicking on the Next button, you'll be able to view the Outdoor

Temperature History, then, the Return History followed by the DHW History.

CONFIGURATION

Button: MENU/<Maintenance>/<Configuration>

• This menu option provides a consolidated view of the Startup settings.

• Additional settings will be available by selecting the NEXT option.

S8 V1.00

Outdoor reset

Heating-BreakOnRise

Day/Night Schedule

DHW Parallel

BACK NEXT

8 X On/Off

PID,Fault Stgs Off

BACK NEXT

DISPLAY

The S8 display layout provides a variety of information that gives an immediate picture of

the operation status. The display shows four heating or cooling units at a time. The two

middle buttons scrolls the screen to view additional boilers. Moreover, all the information is

brightly displayed. It can be viewed in brightly or dimly lit rooms.

• The buttons' functionality changes based on the screen and menu level. The buttons'

functionality is displayed on a dark background on the screen bottom line.

• Horizontal arrows are to scroll through the available stages.

• Vertical arrows are to scroll through the menu functions

when in menus or to change values of settings when in its

specific screen.

Sys=

155

F OD=

58

F

DHW all (200 F)

<AB > DE GH JK
HI HI LO ----

BOILER

MENU

Outdoor Temp

System Temp

Message Display Line

Units and their

Status

Button functions

Button

DISPLAY OUTPUT STATUS

The S8 unit sequencing status gives immediate access to each unit status. The following list show all possible boiler status:

• <AB>

Two-Stage unit and Unit AB is the Lead in sequencing. (Brackets indicate Lead Stage).

• ---

Unit is de-energized. The unit Mode is set to Auto.

• STB

Unit is set to be a Standby Unit.

• HI

Unit highest stage is active. The unit Mode is set to either Auto or Standby.

• MED

Unit Middle stage is active. Available in Three-stage units only. The unit Mode is set to either Auto or Standby.

• MHI

Unit Middle High stage is active. Available in Four-stage units only. The unit Mode is set to either Auto or Standby.

• MLO

Unit Middle Low stage is active. Available in Four-stage units only The unit Mode is set to either Auto or Standby.

• LO

Unit Lowest stage is active. The unit Mode is set to either Auto or Standby.

• ON

All Unit Stages are set to ON.

• OFF

All Unit Stages are set to OFF or unit does not exist.

• C/E

Unit on Extension panel is not communicating back to the S8..

Unit Pumps are being controlled by the S8.

Unit Valves are being controlled by the S8.

DISPLAY MESSAGES

The S8 normal display layout reserved the second line for message indications. The following is a list of the most common Message

Display Line information:

• Summer

The control is set to Summer. No heat is active.

• Winter

The control is set to Winter. No cooling is active.

• Outdoor Cutoff

The Outdoor temperature is above the Outdoor Cutoff in heating or below it in cooling.

• Shutdown Active

The Shutdown Terminals are Shorted. No heating or cooling units will be active.

• Shutdown by EMS

The EMS is below 2mA or above 22mA

• DHW Call (171˚F)

There is a DHW (Domestic Hot Water) call. The S8 will Raise system Set Point to the indicated

temperature. DHW increases calculated temperature to 200˚F or Max Water Temperature, whichever

is lower.