INSTALL THE SENSORS

SYSTEM SENSOR INSTALLATION

LOCATING THE SYSTEM SENSOR

• Put the System sensor approximately 10' feet past the last heating/cooling unit

on the common supply header but before any major takeoffs.

• The sensor must be located where it sees the output of all the stages. If a unit

is piped so that the sensor does not see its output, the S8 will not sequence the

units correctly.

• Only use a Standard Brass Tube sensor (CA002400 or equivalent).

• The sensor wires can be extended up to 500' using a shielded 2-conductor

cable (Belden #8760 or equivalent). Do not ground the shield at the sensor

but at the panel using one of the terminals marked with an “O”.

• Do not run sensor wires in conduit with line voltage wiring.

IMMERSION HEATING SYSTEM SENSOR (HSS) INSTALLATION

• Install a 3/8"ID immersion well (CA002500 or equivalent).

• Insert the sensor probe of the supplied sensor into the well.

STRAP-ON HEATING SYSTEM SENSOR (HSS) INSTALLATION

• Strap the sensor to the pipe using metal clamps. Do not over tighten the

clamp.

• Strap pipe insulation around the sensor and pipe.

Immersion Well

3/8" ID 1/2" NPT

Heating System

Sensor

Common Supply Pipe

Sensor Probe

Immersion Heating System Sensor

Shield

Common Supply Pipe

Sensor Probe

Strap-On Heating System Sensor

Shield

Pipe Insulation

Immersion Well

3/8" ID 1/2" NPT

Heating System

Sensor

Common Supply Pipe

Sensor Probe

Immersion Heating System Sensor

Shield

Common Supply Pipe

Sensor Probe

Strap-On Heating System Sensor

Shield

Pipe Insulation

CAUTION

If the System Sensor can not sense the

correct system water temperature being

supplied to the building, the S8 will not

provide comfortable heat/cool levels. Be

sure that it is located on a main supply

pipe which can not easily be isolated

from the system.

OUTDOOR SENSOR INSTALLATION

• Only use the Laars sensor included with the unit.

• Locate the sensor in the shade on the north side of the building. The sensor

should never be in direct sunlight.

• Be sure the location is away from doors, windows, exhaust fans, vents, or

other possible heat sources.

• The sensor should be mounted approximately 10' feet above ground level.

• Mount the sensor clip base to the outside of the building. Insert the sensor in

the middle and snap close the clip on the sensor.

• The sensor wires can be extended up to 500' using shielded 2-conductor cable.

Do not ground the shield at the sensor but at the control using the terminal

marked with an “O”.

• Do not run sensor wires in conduit with line voltage wiring.

WARNING

The S8 is an operating control only. All equipment must have all

safety and limit controls required by code. It is the responsibility

of the installer to verify that all the safety and limits are working

properly before the S8 is installed.

CAUTION

Determining the proper location for the Outdoor Sensor is very

important. The S8 will base its operation on the outdoor temperature

information it receives from this location. If the sensor is in the

sun, or covered with ice, its reading will be different from the actual

Outdoor temperature (OD).

10' Minimum

Outdoor Sensor

Low Voltage
Sensor Wires

Sensor Clip