Fuel Supply Pump – Check:

a)

Fuel Supply Pump pressure and operation.

Test Procedure – Fuel Supply Pump pressure:

a)

Disconnect all harnesses at the G-II PCM.

b)

Disconnect the fuel supply line.

c)

Loosen and back out the burner head mounting (2) bolts five to six turns

allowing enough room to rotate the burner head 15° counter-clockwise

and remove.

d)

Remove ignition electrode assembly. Use a flat head screwdriver to pry

the electrode assembly out.

e)

Remove the flame shield. Rotate to match the mounting square.

f)

Disconnect the Fuel Solenoid Valve and Ignition Module connectors at the

G-II PCM. Ensures that fuel will not spray and/or light during testing.

g)

Remove the Fuel Supply Pump test port plug located behind the Fuel

Solenoid Valve and install test gauge PK0067.

h)

Reconnect the power and switch harnesses at the G-II PCM.

i)

Reconnect the fuel supply line.

j)

Switch the PROHEAT on and read the fuel pressure (should be 5 – 10 PSI):

If the pressure is out of range, Go to Fuel Supply Pump cleaning, page 4-18.

If the pressure reads OK, review Fuel System troubleshooting, page 4-5.

START: Fuel System Step 7

(1 Flash)

Figure 4-19: Burner Head Removal and Fuel Pressure Test.

GAUGE (P/N PK0067)

FUEL SUPPLY PUMP TEST PORT

FUEL

SOLENOID

VALVE

FLAME

SHIELD

FUEL TEST PORT

IGNITION

ELECTRODE

ASSEMBLY

WARNING

Spilt fuel is flammable.

WARNING

To avoid the risk of shock and to

ensure that the PROHEAT does not

fire, disconnect the Ignition Module

connector at the G-II PCM.

NOTICE

Leaving the Dual Mode Temperature

Sensor disconnected ensures that

the burner head will enter Cool Down

(Purge) mode and run for a maximum

of three minutes.

MOUNTING EARS (2)

MOUNTING BOLTS (2)
TORQUE = SEE SECTION 1.3

COOLANT PUMP

SWITCH INPUT

DUAL MODE TEMP
SENSOR

POWER

FUEL INLET

NOTICE

All plugs/harnesses must be rein-

stalled into the G-II Proheat Control

Module (G-II PCM) before heater

goes back into service.