Scenario 5 Set Output Relays

Select Detector Interface and Route Relays:
1)
Click the Detector Interface button to select the
type of detector/controller interface to be used ( BIU
#1 Card File ).
2) Click the Ph- button to select Phase group 8R.
Note that the line zones corresponding to the selected
phase group turn green. All others are magenta.
3) Click the RI/Card= button to select the number
of relays per card = 2 . Click the RI Slot= to select
the card file slot used= 2.
4) After selecting the RI/Card=2 and the RI Slot=2,
the number detector channels (D1, D2, etc.) that are
shown changes corresponding to this selection.
5) Click the Ext= and the Dly= to select the
Detection Extension in seconds and the Detection
Delay in seconds.
6) Click N, Or, And button to select logic for
combining (N=Not Used) Phase Groups into
Detector Channels.
7) To clear the settings for the selected Phase group
or for all Phase groups click the Clear or the Clear
All
button.

1

2

3

4

7

5

BIU #1 Card file Detector/Controller Interface with 2 Relays per SVS-1 card, Slot 2 used, and 3 Phases (Line Zone Groups)

Phase 3L, Detection Delay=0 sec, Detection Extension=0, Route to Detector Channel D1
Phase 8T, Detection Delay=0 sec, Detection Extension=0, Route to Detector Channel D2

Phase 8R, Detection Delay=2 sec, Detection Extension=2, Route to Detector Channel D2

6

Specifies Routing to Onboard Output Relay
Connector (1, 2, .., 10 0-Disables) for shelf
mount SVS-1