Echelon Neuron User Manual

Page 138

Advertising
background image

130

Neuron Exporter Errors (NEX)

NEX#

Description

42

Malformed or missing parameter record '<tag>' in dependency file <file>

[NEX#42]

Malformed or missing parameter record in dependency file <file>. See
error message for failure details. Attempt to fix with clean and complete

rebuild.

43

Can not compute communication port control byte [NEX#43]

Cannot compute communication port control byte. Verify that your
standard transceiver parameter database (stdxcvr.xml) has not been

corrupted. An update might be available from the

www.lonmark.org

website.

44

Unknown reason [NEX#44]

Failure to compute communication parameters, no reason given.

45

Internal error [NEX#45]

Internal error when calculating communication parameters.

46

Invalid data [NEX#46]

Invalid data caused error when calculating communication parameters.
Verify that your standard transceiver database (stdxcvr.xml) has not been

corrupted. An update might be available from the

www.lonmark.org

website.

47

Unable to compute CP configuration for transceiver <xcvr> [NEX#47]

Unable to compute the CP (Communications Parameters) configuration.

See error message for failure details. Verify that your standard transceiver

database (stdxcvr.xml) has not been corrupted. An update might be
available from the

www.lonmark.org

website.

48

Unrecognized encoded clock rate value <value> [NEX#48]

Unrecognized clock ID. Currently supported encoded clock ID values range

from 0 (625kHz) to 7 (40MHz).

49

Unable to compute end-of packet wait time for single-ended or differential mode

transceiver <xcvr> with hardware clock ID <id> [NEX#49]

Unable to compute the end-of packet wait time for a single-ended or
differential mode transceiver. This is most likely caused by a very fast-

running Neuron chip, combined with a slow channel type. Reduce the clock

speed and see if the problem persists.