Echelon Neuron User Manual

Page 139

Advertising
background image

Neuron Tools Errors Guide

131

NEX#

Description

50

The transceiver's general purpose data record seems malformed: <gp data>

[NEX#50]

The transceiver’s general-purpose data record seems malformed. Verify
that your standard transceiver database (stdxcvr.xml) has not been

corrupted. An update might be available from the

www.lonmark.org

website.

51

The device's clock rate (encoded value <id>) and the transceiver's

communication rate (encoded value <id>) result in an invalid communication

clock divider value. One of the two input rates might be invalid [NEX#51]

The device's clock rate and the transceiver’s communication rate result in
an invalid communication clock divider value. One of the two input rates

might be invalid. See the error message for failure details. Try increasing

or lowering the Neuron clock speed.

52

The transceiver requires a minimum clockrate which is higher than the device's

configured input clock speed [NEX#52]

The transceiver requires a minimum clock-rate that is higher than the

device's configured input clock speed. This combination cannot be used;

you must choose a higher clock rate or a different transceiver.

53

The encoded value for the device's clock input of <id> is not within the

supported range of <min> to <max> [NEX#53]

The encoded value for the device’s clock input is not within the supported

range. See error message for failure details.

54

The encoded value for the channel's minimum clock rate of <id> is not within

the supported range of <min> to <max> [NEX#54]

The encoded value for the channel's minimum clock rate of <id> is not

within the supported range. See error message for failure details. Verify

that your standard transceiver database (stdxcvr.xml) has not been
corrupted. An update might be available from the

www.lonmark.org

website.

55

Unable to determine preamble length using transceiver <xcvr> [NEX#55]

Unable to determine the preamble length. See error message for failure

details. Verify that your standard transceiver database (stdxcvr.xml) has
not been corrupted. An update might be available from the

www.lonmark.org

website.

56

Unable to determine packet cycle duration using transceiver <xcvr> [NEX#56]

Unable to determine the packet cycle duration. See error message for
failure details. Verify that your standard transceiver database

(stdxcvr.xml) has not been corrupted. An update might be available from

the

www.lonmark.org

website.