Neuron Tools Errors Guide

13

LCL#

Description

7

The encoded value for the device's clock input of <id> is not within the

supported range of <min> to <max> [LCL#7]

An invalid encoded clock value has been used to describe the hardware
clock speed. See LCL#2.

8

The encoded value for the channel's minimum clock rate of <id> is not within

the supported range of <min> to <max> [LCL#8]

An invalid encoded clock value has been specified for the channel's
minimum clock speed. This value originates from the standard transceiver

database, and the presence of this problem indicates a corrupted or

incorrect database record. Verify that your standard transceiver database
(stdxcvr.xml) has not been corrupted. Re-install the product and choose the

Repair option when prompted.

9

Unable to compute media access control values (raw transceiver data): the

specified Neuron clock frequency is too high for the transceiver [LCL#9]

This error condition is unavoidable for some combinations of (typically)
high Neuron clock rates and (typically) slow channels. A different

operating mode of the same transceiver or a lower Neuron clock rate might

solve the problem.