6 fault alarms, Alarms, fault, Battery, low – Heath Consultants GT Series User Manual

Page 117: Fault alarms, Fault, zero, Low battery, Zero fault, 6 fault alarms -13

Advertising
background image

11-13

ALARMS

11.6 FAULT ALARMS

Refer to Alarms Table 11.1 to identify the audible / visual

indication for any of the following faults.

11.6.1 Low Battery
The battery symbol

is displayed on the screen

intermittently with

LO

. When the instrument’s battery

power is low, i.e. approximately 30 minutes operating

time remaining, the audible alarm sounds once every two

seconds and the Orange LED flashes. Recharge the

battery or replace the alkaline batteries if using alkaline

batteries.
The Low Battery flag

flashes when approximately

three (3) minutes operating time remains. The audible alarm

sounds once every second and the Orange LED illuminates

constantly. After three (3) minutes the instrument

automatically switches off.
Note: Both audible and visual gas alarms continue to

operate after the low battery warning message

appears.

11.6.2 Zero Fault
A “ZERO FAULT” flag and a flashing spanner symbol

appear after warm-up and after entering a mode if the

instrument is switched on in the presence of gas or the

instrument has been unable to zero all sensors correctly.
The audible alarm sounds, and the orange fault LED

flashes. If the user is in a mode where the faulty sensor

is used the orange LED is on, continuously.
It is strongly recommended the instrument is returned to a

gas free area. Switch the instrument off and then switch

on again in clean air. If the fault persists, return the

instrument for service.

Advertising