Initializing

The Automatic Setup module is receiving its settings from the operator
terminal. This message is normally seen only for a brief time.

Section 6.2

Counterbalance and Cushion “Fault” Messages


None

No error present


Transducer Fail

The pressure transducer gave a reading that is out of its normal range
or gave no reading at all. Check that the transducer cable is still
plugged in. If it is, check for cable damage. If the cable checks out
the transducer may need to be replaced.


Could not Fill

The system was unable to make progress when trying to raise the air
pressure. This could be a bad connection to the fill valve, a failed fill
valve, or no plant air pressure. Probably the most common cause
would be a bad air leak in the system.


Could not Dump

The system was unable to make progress when trying to lower the air
pressure. Probably a bad connection to the dump valve or a failed
dump valve.


Max. Press. Exceeded

The air pressure exceeded the maximum pressure programmed in the
configuration menu. Probably indicates a leaking fill valve or bad
wiring causing the fill valve to be on too long.


Not at Min. Pressure

The air pressure is not at the minimum pressure programmed in the
configuration menu.


A/D converter Fail

The A/D converter on the base card of the auto-setup module is not
responding correctly. This will prevent operation of all air controlled
systems. If the air system is using a type “C” valve (see Section 3.1),
it can be turned OFF in the configurations screen and will revert to
manual control.


Config Data Bad

The configuration data for this system was corrupted. The information
in the configuration menu for this system must be reentered.


Pressure Switch Low

There is a pressure switch on the input air supply to the air valves. If
the input air pressure is too low then the system could open the fill
valve intending to raise the pressure but instead vent some air back
into the air supply. The system will not fill as long as the pressure
switch is low.


Sys not Detected

The hardware necessary for the system cannot be detected. For
example if it was attempted to turn on an air system AS1 and an air
system card was not installed in slot AS1, this error would appear.
This could be either defective hardware or missing hardware.