Counterbalance and Cushion “Status” Message


At Pressure

The air system is within tolerance of its target pressure.


Filling

The system is filling (raising the air pressure).


Dumping

The system is dumping (lowering the air pressure).


Pressure High

The air pressure in the system is too high.


Pressure Low

The air pressure in the system is too low.


System Off

The system has been turned off in the configuration menu. The
pressure will still be displayed if the transducer is working properly.
In addition, if the system is equipped with a type “C” integrated valve
(see section 3.1), the air pressure may still be adjusted with the manual
regulator.


Vented

A pressure setpoint of 0 psi was entered for an air system. The dump
valve is left open in this position. This is a stop condition for the
counterbalance system.

Section 6.4

Slide Adjust “Fault” Messages


None

No errors present


Up/Down Reversed

The “Up” relay has been connected to the “Down” side of the motor
starter and vice versa. The system checks position when moving the
slide and generates this message if it goes in the opposite direction
from that intended.


Slide Did Not Move

If the slide does not move within approximately 2 sec this error will be
generated. Possible causes are counterbalance pressure so far off that
the slide adjust motor cannot overcome it, wiring problems, starter
overloads, a picofuse blown on the slide adjust board, or other
mechanical failures.


Up Relay Open

The “Up” solid state relay on the slide adjust board failed open.
Indicates a hardware failure of the relay.


Up Relay Shorted

The “Up” solid state relay on the slide adjust board failed shorted.
Indicates a hardware failure of the relay.


Down Relay Open

The “Down” solid state relay on the slide adjust board failed open.
Indicates a hardware failure of the relay.