5.- BASIC FEATURES

CIR-eQ analyzer is a programmable measurement unit that measures, calculates and

records the main electrical quality events in single and three-phase electrical networks

in its memory. We must highlight the following concepts:


Serial number:
The serial number of

CIR-eQ is an important parameter, since all files

generated by the unit must be identified with that number. The 10-digit serial number

is written on the rear features label of CIR-eQ.

Programming: The unit is programmed with the setup software

CIR-e.exe. The

application is stored in the SD card supplied with the unit.

Display: The visualization of the quality events is done with Power Vision and Power

Vision +.

Installation:

The analyzer can be installed to analyze balanced (3 wire) or unbalanced (4

wire) single and three-phase networks. The unit must be powered with the auxiliary

power supply cables in any of the connection options. The auxiliary power supply

wires of the unit are Brown and Green.

Measurements: The analyzer takes 128 samples per cycle of the variables in true root

mean square (TRMS). With all of the samples taken, the unit calculates the arithmetic

mean during the recording period selected by the user. The analyzer also records the

maximum and minimum values measured during each period. To take these

measurements, the analyzer has four voltage inputs.

Recording:

The unit has a 1 Gb external SD memory, FAT16 format, which stores the

parameters measured or calculated by the analyzer. We must highlight the following

features:

Stores the quality events detected depending on configuration.

Stores the parameters instantly (measured for a selected period).

Stores the maximum and minimum values of the recording period selected.

The SD memory can be expanded to 2 Gb.

With SD memory of 1Gb the period estimated to register (without EVENTS) is:

Register period

Registering time

1 minute

7 year and 6 months

10 minutes

75 year and 11 months

120 minutes

455 year and 7 months