Electrical features – CIRCUTOR CIReQ User Manual

Page 9

Advertising
background image

_______________________________________________________

_________________________________________________________________________________________________________

CIR-eQ User’s Manual

9 of 36

POWER LED

is on when the unit is powered. It is off when the unit is not powered.

The START/STOP

is used to start or stop the recording of quality events of the network.

Hold the button during

3 seconds.

(*) The REC LED

has three basic modes. When it is off, the unit is not recording

information. When it is permanently on, the unit is recording electrical parameters, which

are stored in the SD memory card. When the REC LED is flashing, there is an error in

the SD memory card. The REC LED can be flashing for the following reasons:

No memory card inserted in the unit's SD card slot.

The memory card inserted does not have the correct format or data can not be

written. (for example, if the card is writen protected or it has a FAT32 format; in

that case change the format of the memory card to

FAT16).

(**) The LED L1, L2 or L3 start flashing to indicate that there is an incorrect connection.

The phase LED start flashing when R-S-T sequence is not correct.

CIR-eQ LED’s start flashing to indicate a connection error.

The unit has been installed correctly when the LED’s are permanently on.

4.1.- ELECTRICAL FEATURES

Power supply circuit (connector B, brown and green wires)

AC voltage

100…400 Vac

DC voltage

70…315 Vdc

Frequency

50 or 60 Hz

Consumption 100 / 400 Vac

5,2 / 22 VA

Consumption 70 / 315 Vdc

3 W

Measurement circuit

Voltage

10…400 Vac (ph-neutral)

17…690 Vac (ph-ph)

Frequency

45…65 Hz

Accuracy

Voltage

0,5 % of E.S.

Battery

Devices (until 2011)

NiMH

Devices from 2012 or later

BR2032

Devices manufactured before 2012 has rechargeable battery.

Devices manufactured after 2012, have BR2032 battery. We recommend

replacing it every 5 years.

Advertising