CIR-eQ User’s Manual

15 of 36

Serial number: Enter the 10 digits of the serial number of

CIR-eQ unit used to take the

measurements. The serial number identifies each individual unit. It is written on a

label on the back of the analyzer: “serial no.” starting with 0107XXXXXX.

The serial number is used by the application as the data name (identifier). The setup

file generated by the application will have the xxxxxxxx.xst format, where “xxxxxxxx

corresponds to the last eight numbers of the unit's serial number.

Report name: You can enter the name of the file for identification purposes. This field is

limited to 16 characters. For example, you can enter the name of the place where the

measurements are going to be taken.

Register period: The registration period is a value that ranges from 1 to 120 minutes (2

hours) and it corresponds to a time interval during which we use to store the average

of the records taken. The analyzer takes 128 samples per cycle of the signals

measured. The registration period indicates the interval desired to take the weighted

mean of all samples taken and it stores this value in the memory. For example, if you

select a registration period of 1 minute, the analyzer calculates the mean of all

samples of the variables registered during that minute and stores the results in the

memory. From that period, the analyzer also stores the maximum and minimum

values measured.